Product Overview
1
MEP437
PROGRAMMER MODULE
FOR USE WITH THE FIREYE
®
MEC320
MicroM™ CONTROL
WARNING: Selection of this control for a particular application should be made by a
competent professional, licensed by a state or other government. Inappropriate application
of this product could result in an unsafe condition hazardous to life and property.
DESCRIPTION
The Fireye MicroM Series Flame Safeguard Control is a compact, microprocessor based,
modular burner management system designed to provide automatic ignition and continuous
flame monitoring for commercial sizes of heating and process equipment firing any type of
fuel. The advantages of the MicroM are zero dependence on discrete components previ-
ously used for timing functions.
Flame Failure Response Time (FFRT) is determined by the selection of the amplifier mod-
ule. Test jacks are also provided on the flame amplifier module to permit flame signal mea-
surement during operation. For proper and safe application of this product, you must refer
to Fireye bulletin MC-5000 for a detailed description of the various programmer modules,
including installation instructions, amplifier selection, operating sequences for each pro-
grammer module, etc.
To maximize safety the MEP437 provides early spark termination followed by a pilot prov-
ing period. This prevents the unwanted detection of spark generated by a maladjusted pilot
and spark assembly. Refer to Figure 3 on page 4, Sequence Timing.
Unique to the MEP437 is the ability to check the main valve proof of closure switch also
referred to the fuel valve end switch. This switch must be connected to terminals L1-7. The
proper state of this switch checked after the running interlocks connected to terminal 6 are
closed. Refer to Figure 2 on page 3.
Functions provided on the MEP437 programmer:
1. Operating temperature: -40F (-40C) to 140 F (60C)
2. MEC320 type chassis required
3. Purge time: User selectable 0, 5, 15, 30, 60, 90, 120, 240 seconds
4. Pilot trial for ignition period (PTFI): User selectable 5 (closed) or 10 seconds (open) fixed.
5. Pilot solenoid operation, terminal 3 user selectable Interrupted or Intermittent
6. Pilot proving period (ignition terminal 4 de-energized): 5 seconds
7. Main trail for ignition period (MTFI): 5 seconds
8. Action on pilot flame fail: Lockout
9. Action on pilot proving period flame fail: Lockout
10. Action on main trial for ignition period flame fail: Lockout
MP-5401
APRIL 11, 2013