WARNING: Remove power from the control before proceeding.
INSTALLATION
The Programmer Modules are used with the
Fireye modular MicroM Chassis
(P/N MEC320, MEC320RC, MEC320R,
MEC320D and MEC320C for 120VAC and
MEC480 for 230 VAC). They are installed in
the chassis by grabbing hold of the program-
mer module by the ridged finger grips on the
side on the module, aligning the module with
the guide slots on the opening farthest from
the transformer, and inserting the module
into the pin connectors.
LOCKOUT CODES
= NOT LIGHTED
= LIGHTED
= FLASHING
All MicroM chassis are shipped with a convenient peel off label that can be applied to any surface (inside cover) for future reference.
MSGN DESCRIPTION OP CTRL
AIRFLOW
INTLCK
PTFI FLAME ALARM
DEC HEX
6 6 Lockout Line Frequency Noise Detected ●❍❍
7 7 Lockout Flame Fail - PTFI ❍●
15 0F Lockout Fault Unknown ●●
16 10 Lockout Amplifier High Count Fail ❍❍
19 13 Lockout Flame Fail - MTFI ❍❍
20 14 Lockout False Flame - STANDBY ❍●
21 15 Lockout Intrlck Open ●●
22 16 Lockout Intrlck Closed ❍●
24 18 Lockout Chassis Opto ●●❍
37 25 Lockout Flame Fail - AUTO ❍●
39 27 Lockout Fuel Valve State Change ❍❍
54 36 Lockout Check Chassis ❍❍
55 37 Lockout Check Programmer ❍❍
56 38 Lockout Check Amplifier ●❍
58 3A Lockout Amplifier Auto Check Fail ●❍
59 3B Lockout Check BLOWN FUSE ●❍
76 4C Lockout Check Scanner ●●❍
The programmer modules
are designed to fit into the
proper slot only.
DO NOT FORCE
THEM
FIREYE MP-5301