Product Overview

1
®
DESCRIPTION
The Fireye MEP300, MEP304, MEP335 and MEP397 Programmer Modules are used with the Fireye
Modular MicroM control. The MEP300 series programmers provide additional enhancements such as
early spark termination, pilot proving and interrupted or intermittent pilot operation. These programmers
must be used with the MEC320 and MEC480 series chassis. The programmer module incorporates a plug-
in design for easy installation.
The advantages of the Micro M are zero dependence on discrete components previously used for timing
functions. The MicroM, through the use of micro-controller technology, incorporates smart diagnostic
LED’s, smart reset function for multi-burner applications, optional alpha-numeric display output (ED510)
and serial communications via a Modbus Interface. A “check-run” switch is provided on the MEP397 pro-
grammer module to assist in testing size and stabilization of the pilot.
Flame Failure Response Time (FFRT) is determined by the selection of the amplifier module. Test jacks
are also provided on the flame amplifier module to permit flame signal measurement during operation.
For proper and safe application of this product, you must refer to Fireye bulletin MC-5000 for a detailed
description of the various programmer modules, including installation instructions, amplifier selection,
operating sequences for each programmer module, etc.
WARNING: Selection of this control for a particular application should be made by a competent
professional, licensed by a state or other government agency. Inappropriate application of this
product could result in an unsafe condition hazardous to life and property. Installation should not
be considered complete until pilot turndown and other appropriate performance tests have been
successfully completed.
PROGRAMMER MODULE SELECTION
MicroM Programmer Models (For use with MEC320 and MEC480 Chassis)
MEP300 Relight operation, 10 sec. fixed PTFI, 5 second pilot proving period, 5 second MTFI. lockout on flame fail during
PTFI, pilot proving and MTFI. Recycle on air flow open. No post purge. Reset on line voltage.
MEP304 Non-recycle on flame fail, 5 second purge, 10 second fixed PTFI, 5 second pilot proving, 10 second MTFI, inter-
rupted pilot, early spark termination.
MEP335 Non-recycle on flame fail, 30 second purge, 35 second hot surface ignition on terminal 4, 3 second PTFI on terminal
3, 5 second pilot proving period, intermittent pilot, 15 second post purge. Manual reset only.
MEP397 Recycle on main flame fail, 15 second purge, 7 second fixed PTFI, 5 second pilot proving 5 second MTFI, early spark
termination and interrupted pilot. Recycle on air flow failure. No post purge, run/check switch. Reset on line voltage.
MEP300, MEP304, MEP335 and MEP397
PROGRAMMER MODULES
FOR USE WITH THE FIREYE
®
MODULAR
MicroM™ CONTROL TO BE USED
MP-5301
APRIL 4, 2013
U
L
APPROVED
LISTED
C
US

Summary of content (2 pages)