Product Overview

2
WARNING: Remove power from the control and remove the control from its wiring base
before proceeding.
INSTALLATION
The Programmer Modules are used with the
Fireye modular MicroM Chassis
(P/N MEC120, MEC120RC, MEC120R,
MEC120D and MEC120C for 120VAC and
MEC230 for 230 VAC). They are installed in
the chassis by grabbing hold of the programmer
module by the ridged finger grips on the side
on the module, aligning the module with the
guide slots on the opening farthest from the
transformer, and inserting the module into the
pin connectors.
LOCKOUT CODES
= NOT LIGHTED
= LIGHTED
= FLASHING
All MicroM chassis are shipped with a convenient peel off label that can be applied to any surface (inside cover) for future reference.
MSGN DESCRIPTION OP
CTRL
AIRFLOW
INTLCK
PTFI FLAME ALARM
DEC HEX
6 6 Lockout Line Frequency Noise Detected 
7 7 Lockout Flame Fail - PTFI 
15 0F Lockout Fault Unknown 
16 10 Lockout Amplifier High Count Fail 
19 13 Lockout Flame Fail - MTFI 
20 14 Lockout False Flame - STANDBY 
21 15 Lockout Intrlck Open 
22 16 Lockout Intrlck Closed 
24 18 Lockout Chassis Opto 
37 25 Lockout Flame Fail - AUTO 
39 27 Lockout Fuel Valve State Change 
54 36 Lockout Check Chassis 
55 37 Lockout Check Programmer 
56 38 Lockout Check Amplifier 
58 3A Lockout Amplifier Auto Check Fail 
59 3B Lockout Check BLOWN FUSE 
76 4C Lockout Check Scanner 
The programmer modules are
designed to fit into the proper
slot only.
DO NOT FORCE THEM
FIREYE MP-5101
3 Manchester Road APRIL 3, 2013
Derry, New Hampshire 03038 USA Supersedes March 27, 2009
www.Fireye.com