Product Overview
2
WARNING: Remove power from the control and remove the control from its wiring base
before proceeding.
INSTALLATION
The Programmer Modules are used with the
Fireye modular MicroM Chassis
(P/N MEC120, MEC120RC, MEC120R,
MEC120D and MEC120C for 120VAC and
MEC230 for 230 VAC). They are installed in
the chassis by grabbing hold of the programmer
module by the ridged finger grips on the side
on the module, aligning the module with the
guide slots on the opening farthest from the
transformer, and inserting the module into the
pin connectors.
LOCKOUT CODES
= NOT LIGHTED
= LIGHTED
= FLASHING
All MicroM chassis are shipped with a convenient peel off label that can be applied to any surface (inside cover) for future reference.
MSGN DESCRIPTION OP
CTRL
AIRFLOW
INTLCK
PTFI FLAME ALARM
DEC HEX
6 6 Lockout Line Frequency Noise Detected
7 7 Lockout Flame Fail - PTFI
15 0F Lockout Fault Unknown
16 10 Lockout Amplifier High Count Fail
19 13 Lockout Flame Fail - MTFI
20 14 Lockout False Flame - STANDBY
21 15 Lockout Intrlck Open
22 16 Lockout Intrlck Closed
24 18 Lockout Chassis Opto
37 25 Lockout Flame Fail - AUTO
39 27 Lockout Fuel Valve State Change
54 36 Lockout Check Chassis
55 37 Lockout Check Programmer
56 38 Lockout Check Amplifier
58 3A Lockout Amplifier Auto Check Fail
59 3B Lockout Check BLOWN FUSE
76 4C Lockout Check Scanner
The programmer modules are
designed to fit into the proper
slot only.
DO NOT FORCE THEM
FIREYE MP-5101