Product Overview
11
®
PROGRAMMER DIPSWITCH SETTINGS
NOTE: THE DIPSWITCHES ARE A ONE TIME, ONE SHOT SETTING. ONCE THE
DIPSWITCHES ARE SET AND THE PLASTIC WINDOW IS MOVED OVER THE
SWITCHES, THE WINDOW CANNOT BE MOVED AND THE DIPSWITCHES AND THEIR SET-
TINGS CANNOT BE CHANGED WITHOUT CAUSING THE CONTROL TO BECOME INOPERA-
BLE.
The MP230, MP230H, and the MP560, MP561, MP562 Programmer Modules have a series of 8
dipswitches which allow the user to program the purge timing, trial for ignition timing, and recycle/
non-recycle operation of the control. These dipswitches are programmed only ONCE, before the ini-
tial operation of the control.
THE PLASTIC WINDOW MUST BE MOVED OVER THE SWITCHES IN ORDER FOR
THE PROGRAMMER TO OPERATE BEYOND PURGE.
Purge Timing
Dipswitches # 1 through #5 are used to select the purge timing for the control. The available timing
selections are 5 seconds, 7 seconds, 30 seconds, 60 seconds, 240 seconds, and any combination of
those timings. The timings for these switches are additive. Selecting two or more purge timing
switches will result in a purge timing period equal to the sum of the switches (e.g. selecting switches
# 3, and #4 will cause a purge timing of 90 second: 30 seconds plus 60 seconds). To select the timing
associated with a particular switch, move the switch to the RIGHT (On Position).
NOTE: If all 5 switches are set to the OFF position, the control will lock out after the air flow switch
has been proven closed.
Trial for Ignition
Dipswitches #6 and #7 are used to select the trial for ignition timing for the control. The available
timing selections are 5 seconds and 10 seconds only. See Figure #1. Select ONLY ONE of these two
switches. These switches ARE NOT additive. To select the timing associated with a particular
switch, move the switch to the RIGHT (On Position).
NOTE: If both switches are set to the OFF position, the control will default to a trial for ignition
period less than 5 seconds (e.g.: 3-4 seconds).
If both switches are set to the ON position, the control will default to LOCKOUT.
Recycle/Non-recycle Operation
Dipswitch #8 is used to select either recycle or non-recycle operation of the control. (See APPLICA-
TION AND FUNCTION). To select RECYCLE operation, move the switch to the LEFT. To select
NON-RECYCLE operation, move the switch to the RIGHT.
SWITCH OFF ON
1
2
3
4
5
-
-
-
-
-
5
7
30
60
240
PURGE TIMING *
6
7
-
-
5
10
PTFI
8 RECYCLE NON RECYCLE
* The MP561 programmer module has purge timing selctions of 5, 7, 15, 30 and 60 seconds.