Product Overview

5
®
WIRING BASE (COMMON FOR ALL CONTROLS):
61-3060 Closed wiring base, surface mounting
61-5042 Open wiring base, cabinet mounting
For a complete system, choose one of each of the following:
— Chassis — UV Scanner or Flame Rod
— Programmer Module — Wiring Base
— Amplifier Module
WARNING: Installer must be trained and qualified. Follow the burner manufacturer’s in-
structions, if supplied. Otherwise, proceed as follows:
INSTALLATION OF CONTROL, SCANNERS, AND FLAME DETECTORS
Wiring Base
Mount the wiring base on the burner or on a panel. The location should be free from excessive vibra-
tion and within the specified ambient temperature rating. The base may be mounted in any angular
position.
All wiring should comply with applicable electrical codes, regulations, and local ordinances. Use
moisture resistant wire suitable for at least 90 degrees C. Circuit recommendations are found on
pages 26 through 30. Consult the factory for assistance with non-standard applications.
WARNING: Controls require safety limits utilizing isolated mechanical contacts. Solid state
limit switches are not acceptable and should not be used due to their high leakage currents.
Installing the Programmer and Amplifier Modules
WARNING: Remove power from the control before proceeding.
Select the appropriate programmer and amplifier modules for your application. Remove the dust
cover from the chassis. Insert the amplifier module into the slot in the center of the chassis and gen-
tly push the module into position. Insert the programmer module into the slot at the right side of the
chassis and gently push the module into position.
NOTE: Refer to Programmer dipswitch settings on page 11 for the proper setting of the dipswitches
for those programmers with this feature.
WARNING: Turn off the power when installing or removing the control.
AMPLIFIER
PROGRAMMER