Product Overview
31
®
CAUTION: Control wiring procedures which deviate from those shown in the diagrams may
bypass safety functions designed in the control. Check with the Fireye Representative before
deviating from the recommended wiring diagrams.
M-SERIES II CROSS REFERENCE LISTING
M-SERIES M-SERIES II REPLACEMENT MODULES
Part Number Chassis Amplifier Programmer
Programmer
Dipswitch #8
UVM1D MC120 MAUV1T MP100 N/A
UVM1F MC120 MAUV1 MP100 N/A
TFM1D MC120 MART1T MP100 See Note #1
TFM1F MC120 MART1 MP100 See Note #1
UVM2 MC120 MAUV1 MP230 OFF
TFM2 MC120 MART1 MP230 OFF
UVM3 MC120 MAUV1 MP230 ON
TFM3 MC120 MART1 MP230 ON
UVM3H MC120 MAUV1 MP230H ON
TFM3H MC120 MART1 MP230H ON
UVM5 MC120 MAUV1 MP560 ON
UVM6 MC120 MAUV1 MP560 See Note #2
- N/A — Not Applicable
- Programmer Dipswitches apply to MP230, MP230H, and MP560 Programmers
- Dipswitch #8 sets Recycle / Non-Recycle Operation. (ON = Non-Recycle, OFF = Recycle)
- MP560 Programmer Module has “Check-Run” Switch.
- Note 1: For standing pilot, clip out red jumper on MP100.
- Note 2: Dipswitch #8 - ON when red jumper of UVM6 is clipped. Otherwise, Dipswitch #8 = OFF.
M-SERIES
TIMING CARDS
M-SERIES II
PROGRAMMER DIPSWITCH SETTINGS
#1 #2 #3 #4 #5 #6 #7
MT55 ON OFF OFF OFF OFF ON OFF
MT74 OFF ON OFF OFF OFF ON OFF
MT304 OFF OFF ON OFF OFF ON OFF
MT710 OFF ON OFF OFF OFF OFF ON
MT904 OFF OFF ON ON OFF ON OFF
MT3010 OFF OFF ON OFF OFF OFF ON
MT6010 OFF OFF OFF ON OFF OFF ON
MT9010 OFF OFF ON ON OFF OFF ON
- Dipswitches #1 through #5 set Purge Timing.
- Dipswitches #6 and #7 set TFI Timing.
Dipswitch # Off On
1
-
5
2
-
7
PURGE
3
-
30
TIMING
4
-
60
Values are Additive
5
-
240
6
-
5
TFI
7
-
10
TIMING
8
Recycle
Non-Recycle