Product Overview

26
£
FIGURE 1. TYPICAL MP100, MP100E, MP101, MP230, and MP230H WIRING ARRANGEMENT FOR PILOT
IGNITED BURNER. MC120, MC120R, MC230, MC230R CHASSIS ONLY.
Use moisture resistant wire suitable for at least 90q C.
CAUTION: When powered, 560 VAC across S1, S2 with MAUV1 and MAUV1T; 260 VAC
across S1, S2 with MART1 and MART1T.
FIGURE 2. TYPICAL MP100, MP100E, MP101, MP230, AND MP230H WIRING ARRANGEMENT FOR DIRECT
SPARK IGNITED BURNER MC120, MC120R, MC230, MC230R CHASSIS ONLY.
Use moisture resistant wire suitable for at least 90q C.
CAUTION: When powered, 560 VAC across S1, S2 with MAUV1 and MAUV1T; 260 VAC
across S1, S2 with MART1 and MART1T.
TERMINAL #1 MUST BE DIRECTLY POW-
ERED AS SHOWN WITH 120 VAC WHEN US-
ING MAUV1 OR MAUV1T AMPLIFIER MOD-
ULES IN ORDER TO INITIATE SAFETY
CHECKING CIRCUIT OF UV SCANNERS.
LIMIT
SWITCHES
OPERATING
CONTROL
FUEL
INTERLOCKS
7
BURNER MOTOR
OR
CONTACTOR
8
2
A
6
LOCKOUT
ALARM
KB
KA
AIR FLOW
SWITCH
ELECTRONIC
CIRCUIT
KL KF
S1
S2
3
5
4
1
FLAME
AMPLIFIER
KL-1
KF-1
KF-2
PILOT
MAIN
SPARK
BURNER
CONTROL
SWITCH
H
N
120V (MC120)
230V (MC230)
50/60 Hz
SUPPLY
DISCONNECT MEANS
AND OVERLOAD
PROTECTION REQUIRED
*
** WITH MAUV1 AND MAUV1T AMPLIFIER MODULES,
PRIMARY WINDINGS OF TRANSFORMER ARE TO
TERMINALS #2 & #1.
* WITH MAUV1 AND MAUV1T AMPLIFIER MODULES,
CONNECTION TO KA IS FROM TERMINAL #1.
** WITH MART1 AND MART1T AMPLIFIER MODULES,
PRIMARY WINDINGS OF TRANSFORMER ARE TO
TERMINALS #2 & #7.
MC120/MC230 WITH MAUV1
OR MAUV1T
AMPLIFIER MODULES
**
UV
SCANNER
FLAME ROD
FUEL VALVE
MC120 WITH MART1
OR MART1T
AMPLIFIER MODULES
IGNITION
GAS VALVE
CONNECTION TO TERMINAL #1 IS NOT
REQUIRED WITH MART1 OR MART1T
AMPLIFIER MODULE
***
*** WITH MAUV1 AND MAUV1T,
KB ENERGIZED WHEN
TERM. 1 IS POWERED.
WITH MART1 AND MART1T,
KB ENERGIZED WHEN
TERM. 7 IS POWERED.
LIMIT
SWITCHES
OPERATING
CONTROL
FUEL
INTERLOCKS
7
BURNER MOTOR
OR
CONTACTOR
8
2
A
6
LOCKOUT
ALARM
KB
KA
AIR FLOW
SWITCH
ELECTRONIC
CIRCUIT
KL KF
S1
S2
3
5
4
1
FLAME
AMPLIFIER
KL-1
KF-1
KF-2
PRIMARY MAIN
BURNER
CONTROL
SWITCH
H
N
120V (MC120)
230V (MC230)
50/60 Hz
SUPPLY
DISCONNECT MEANS
AND OVERLOAD
PROTECTION REQUIRED
MC120/MC230 WITH MAUV1
OR MAUV1T
AMPLIFIER MODULES
UV
SCANNER
FLAME ROD
MC120 WITH MART1
OR MART1T
AMPLIFIER MODULES
FUEL VALVE
SECONDARY
SPARK
MAIN FUEL
VALVE (IF USED)
IGNITION
FOR INTERMITTENT IGNITION, CONNECT
TO TERMINAL 3
**
*
** WITH MAUV1 AND MAUV1T AMPLIFIER MODULES,
PRIMARY WINDINGS OF TRANSFORMER ARE TO
TERMINALS #2 & #1.
* WITH MAUV1 AND MAUV1T AMPLIFIER MODULES,
CONNECTION TO KA IS FROM TERMINAL #1.
** WITH MART1 AND MART1T AMPLIFIER MODULES,
PRIMARY WINDINGS OF TRANSFORMER ARE TO
TERMINALS #2 & #7.
CONNECTION TO TERMINAL #1 IS NOT
REQUIRED WITH MART1 OR MART1T
AMPLIFIER MODULE
***
*** WITH MAUV1 AND MAUV1T,
KB ENERGIZED WHEN
TERM. 1 IS POWERED.
WITH MART1 AND MART1T,
KB ENERGIZED WHEN
TERM. 7 IS POWERED.
TERMINAL #1 MUST BE DIRECTLY POW-
ERED AS SHOWN WITH 120 VAC WHEN US-
ING MAUV1 OR MAUV1T AMPLIFIER MOD-
ULES IN ORDER TO INITIATE SAFETY
CHECKING CIRCUIT OF UV SCANNERS.