Product Overview

2
£
SPECIFICATIONS
Supply:
120V (min. 102, max. 132) 50/60 Hz. (MC120/MC120R/MC120P)
230V (min. 196, max 253) 50/60Hz (MC230/MC230R)
Table 1: AMBIENT TEMPERATURE LIMITS
Power Consumption: 12 VA (Operating)
Shipping Weight (Approx.): 3 lbs. (1.4kg)
Table 2: LOAD RATINGS
APPROVALS
Underwriters Laboratories Inc. Factory Mutual System (FM) Approved
Listed Guide MCCZ - File MP 1537
Underwriters Laboratories Inc. Canadian Standards Association
Recognized Components Guide MCCZ2 Guide 300-1-0.2 Class 2642 Oil File LR7989
File MP1537 Guide 140-A-2 Class 2632 Gas File LR7989
Approvals do not apply to MC230 and MC230R Chassis and associated programmers.
MAXIMUM MINIMUM
Control 125q F (52q C) - 40q F (- 40q C)
Scanner UV1A,
UV2, UV8A,
45UV3
200q F (93q C) - 40q F (- 40q C)
Flame Rod
(Tip 2460 F)
1500q F (816q C) - 40q F (- 40q C)
Fireye Terminal Typical Load Maximum Rating & 120V 60 Hz
3 or 4
Individual or combined
Pilot valve(s)
Solenoid valve
Ignition Transformer
125 VA pilot duty (solenoid valve) plus
250 VA (Transformer)
5 Main Fuel Valve(s)
125 VA pilot duty (solenoid) or
25 VA pilot duty (solenoid) and
400 VA (opening) motorized
8 Motor or contactor
Motor normally energized and de-energized by the
operating control whose rating must be suitable. Termi-
nal 8 rated to de-energize 9.8 FLA, 58.8 LRA, on safety
lockout.
A Alarm 50 VA, pilot duty
Minimum load requirement = 100mA