Product Overview

4
FIGURE 2. TYPICAL APPLICATION - MBPF-100S
WARRANTIES
FIREYE guarantees for one year from the date of installation or 18 months from date of manufacture of its products to
replace, or, at its option, to repair any product or part thereof (except lamps, electronic tubes and photocells) which is
found defective in material or workmanship or which otherwise fails to conform to the description of the product on
the face of its sales order. THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE
MAKES NO WARRANTY OF MERCHANTABILITY OR ANY OTHER WARRANTY, EXPRESS OR
IMPLIED. Except as specifically stated in these general terms and conditions of sale, remedies with respect to any
product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replacement or repair
as above provided. In no event shall Fireye be liable for consequential or special damages of any nature that may arise
in connection with such product or part.
Test Signal
Terminal #10
Flame Condition RF Relay “FLAME ON” LED “FLAME FAIL” LED
0OFFOFFOFF OFF
0 ONONON OFF
12-120 vac/vdc OFF ON OFF ON
12-120 vac/vdc ON ON OFF ON
6
7
8
9
10
11
5
4
3
2
1
UV ScannerUV Scanner
Flame RodFlame Rod
yellowyellow
blueblue
ProgrammableProgrammable
ControllerController
9 10 0 11 1 1231 2 3
878 7 6 5 4
120VAC120VAC
50/60Hz50/60Hz
Analog Signal 8Analog Signal 8
-
12 VDC12 VDC
12-120 VAC/DC Test Signal12-120 VAC/DC Test Signal
NONOC
NC
NC
NONO
C
NC
NC
2A2A
L
On/Off
On/Off
NT
AF
TF
FR
RTN
UV
NO
COM
NC
LN
N
Signal ReturnSignal Return
60-2726
FLAME ROD RETURN
(WHERE APPLICABLE)
In this application, the programmable
controller (PLC) can test the flame relay
for proper function by applying voltage
to Pin #10 and monitoring the contact
action on Pins #4, #5 and #6 (Pin#4
opens and Pin #6 closes).
NOTE: If Pin #10 is not used for remote testing, it should be jumpered to Pin #1 (neutral).
WIRING
BASE
UV7SC
UV SELF CHECK
SCANNER
B
D
A
C
(WH) 120VAC
(RD) NEUTRAL
(GN) RETURN
(BK) SIGNAL
SPECIAL CONDITIONS OF USE
1. The equipment shall be installed in compliance with the enclosure, mounting spacing and segregation requirements
of the ultimate application.
2. Line voltage and extra-low voltage wiring to and from this device is intended to be wired in the field to become
part of a Class 1 circuit only.
MBPF-100S
and
NOTE:
TERMINALS 1 & 8 ARE
INTERNALLY CONNECTED
MB-600PF
ONLY
FIREYE MBPF-1001
3 Manchester Road APRIL 4, 2013
Derry, New Hampshire 03038 USA Supersedes September 12, 2011
www.fireye.com