DESCRIPTION
The MBPF-100S, MB-600PF, MBPF-200S and MBPF-202S modules provide visual
indication and electrical output that signal the user regarding flame presence in a
combustion chamber. The module uses Fireye optical ultra-violet scanners and/or
flame rod to sense flame presence independently or as components in a burner man-
agement system. Many operational characteristics are provided including:
• UL recognized and FM approved-MBPF-100S, MB-600PF
• FM approved - MBPF-200S, MBPF-202S
• Self-contained: 120 VAC, 50/60: MBPF-100S, MB-600PF
220 VAC, 50/60: MBPF-200S, MBPF-202S
• UV detection or flame rod or both
• Flame ON LED
• User controlled Flame Fail LED
• Analog output test points permits direct reading of flame signal
• Uses standard 11-pin relay base
• Panel surface or DIN-rail mounting
• Remote testing of contacts available
• Self-check scanner available for MBPF-100S and MB-600PF
Check with Fireye for more details by contacting your local distributor or by check-
ing the Fireye home page at www.fireye.com.
NOTE: When the MBPF modules are used, additional means must be furnished to provide those func-
tions usually provided by flame safeguard control systems to meet local regulations (i.e.: safe start
check, valve closure, starting and running interlocks, safety timings, etc.).
NOTICE: When Fireye products are combined with equipment manufactured by others and/
or integrated into systems designed or manufactured by others, the Fireye warranty, as stated
in its General Terms and Conditions of Sale, pertains only to the Fireye products and not to any
other equipment or to the combined system or it’s overall performance.