Product Overview

6
£
Avoid wire loops and poor groundings.
Keep high voltage ignition wires well away from scanner wires.
The 45UV5 self-check scanner has four 6 foot (1800mm) leads:
45UV5-1005 & 1105:
Two black leads which power the shutter from the associated control and two red leads which drive
the UV tube and carry the flame signal to the control amplifier.
45UV5-1006, 1007, 1008 & 1009:
Two black leads which power the shutter via L1 & L2 and two red leads which drive the UV tube and
carry the flame signal to S1 & S2 on the control.
If it is necessary to extend the scanner wiring, the following instructions apply:
Scanner wires should be installed.in a separate conduit. The wires from several scanners may be
installed in a common conduit.
45UV5-1006, 1007, 1008, 1009.
1. Selection of wire
Use #14, 16, or 18 wire with 75 C, 600 volt insulation for up to 100 foot distances (signal
loss approximately 20% at 100 feet).
Asbestos insulated wire should be avoided.
Multiconductor cable is not recommended without prior factory approval.
Extended Scanner Wiring. For extended scanner wiring up to 1500 feet, and for shorter
lengths to reduce signal loss, use a shielded wire (Belden 8254-RG62U) coaxial cable, or
equal for each red wire of the 45UV5. The ends of the shielding must be taped individually
on both ends and not grounded.
For multiple burner installations:
2. Distances are decreased when more than one set of scanner leads are installed in a common con-
duit. For example, the maximum distance for 2 scanners is 750 feet and for 3 or more scanners
the distance decreases to 500 feet.
3. High voltage ignition wiring should not be installed in the same conduit with flame detector
wires.
WARNING: DO NOT CONNECT 45UV5 SCANNERS IN PARALLEL
16-24VDC TO CONTROL
SHUTTER
45UV5-1005, 1105
UV TUBE
560 VAC (RED)
BLACK L1, L2
SHUTTER
45UV5-1006, 1007, 1008, 1009
UV TUBE
RED S1. S2
ON CONTROL