Product Overview
2
£
absence of flame; the frequency of the pulses is a measure of flame intensity. Pulses generated by the
scanner are transmitted to a compatible Fireye control via scanner wiring.
FEATURES
The components are contained in a cast aluminum housing sealed with an oil-resistant gasket. The
quartz lens is a planoconvex design, resulting in increased sensitivity. Also included in the scanner is
an electromagnetic shutter that permits a self-checking circuit to verify that the scanner and signal
circuits are producing valid flame presence or absence information. During the shutter closed period,
the detector’s optical path is blocked from flame radiation, allowing the amplifier control to verify
the proper operation of the ultraviolet tube. While the shutter is open, flame presence or absence is
detected. The resultant scanner output (while flame is detected) is a continuous, periodically inter-
rupted, pulsed flame signal which is a prerequisite for energizing the associated Fireye control’s
Flame Relay.
SPECIFICATIONS
FIGURE 1.
SPECIFICATIONS TABLE
NOTE 1: Flame-Monitor, EUVS4; D-Series, 72DUVS1T, 72DUVS4; MicroM, MEUVS1, MEUVS4; FlameWorx; MBUVS-301D, MBUVS-
311D, BurnerLogix, YB110UVSC.
NOTE 2: Models 1006, 1007, 1008 and 1009 have shutter drive circuitry within the scanner. Models 1005 and 1105 have shutter drive circuitry
in compatible control.
NOTE 3: When using FlameWorx modules, MBUVS-301D and MBUV-311D, refer to bulletin FWX-1001 for proper wiring terminals.
NOTE 4: Controls no longer manufactured.
NOTE 5: 45-1005 and 45-1105 are NOT FM approved for use with 25RU8-4580, 25SU5-4013/4113-4113T/4116T-4116/4119.
NOTE 6: Extended operating voltage and temperature range applies to engineering code 3 and higher.
MODEL NO. THREADS NOMINAL SHUTTER
TOTAL CYCLE PERIOD
VOLTAGE 50/60 HZ TEMP. RANGE USE ONLY WITH
CONTROL MODELS
TERMINALS
SHUTTER
(BLK)
SIGNAL (RED) MAX. MIN. SIGNAL SHUTTER
45UV5-
1005
1" NPT
Regulated by
control
17VDC
560VAC
200q F
(93q C)
- 40q F
(- 40q C)
25RU8-4580
25SU5-4013/4113
-4113T/4116T
-4116/4119
-4018
• See note 4
• See note 1, but
must use
61-5745-3 to
control shutter
12 & 13
All
Models
14 & 15
All
Models
45UV5-
1105
1" BSP
560VAC
45UV5-
1006
1" NPT 1.4 sec. closed
3.5 sec. open
102VAC to
264VAC
See note 6
560VAC
200q F
(93q C)
See
Note 6
- 40q F
(- 40q C)
D-Series
72DUVS1 Only
S1-S2 L1-L2
45UV5-
1007
1" BSP .4 sec. closed
3.6 sec. open
560VAC - 40q F
(- 40q C)
See note 1 S1-S2
See note 3
L1-L2
45UV5-
1008
1" BSP .4 sec. closed
3.6 sec. open
560VAC - 40q F
(- 40q C)
See note 1 S1-S2
See note 3
L1-L2
45UV5-
1009
1" NPT .4 sec. closed
3.6 sec. open
560VAC - 40q F
(- 40q C)
See note 1 S1-S2
See note 3
L1-L2
3/8” -18 NPT OR
3/8” - 18 BSP-PL
45q
(51)
8 1/4" (210)
2"
(51)
MIN
CLEARANCE
PURGE AIR CONNECTION
4" (102)
1 11/16”
HEX.
(43)
1" - 11 1/2 N.P.T.
(BSP-S1)
SIGHT PIPE
CONNECTION
HOUSING MATERIAL:
ALUMINUM
REQUIRED
TO REMOVE
2
TYPE 45UV5