System Capacity
Annunciators ...................................................................... 8
Electrical Specifications
MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ,
1.0 A
MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ,
3.90 A
MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ,
2.20 A.
Wire size:
minimum 14 AWG (2.0 mm
2
) with 600 V insula-
tion, supervised, nonpower-limited
Cabinet Specifications
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x
0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x
16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring
(TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.
Shipping Specifications
Dimensions:
20.00" (50.80 cm.) high
22.5" (57.15 cm.) wide
8.5" (21.59 cm.) deep.
Weight: 27 lb (12.20 kg)
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 – 27°C/60 – 80°F.
Agency Listings and Approvals
The listings and approvals below apply to the basic MS-5UD-3
and MS-10UD-7 control panels. In some cases, certain mod-
ules or applications may not be listed by certain approval
agencies, or listing may be in process. Consult factory for lat-
est listing status.
UL Listed: File S624
FM Approved
CSFM: 7165-0075:214
MEA: MEA: 333-07-E
NOTE: For ULC-listed models, see df-60440.
NFPA Standards
The MS-5UD/MS-10UD(E) Series complies with the following
NFPA 72 Fire Alarm Systems requirements:
– LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
–AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTMF).
REMOTE STATION (Automatic, Manual and Waterflow)
(Where a DACT is not accepted, the alarm, trouble and
supervisory relays may be connected to UL 864 listed
transmitters. For reverse polarity signaling of alarm and
trouble, 4XTMF is required.)
–PROPRIETARY (Automatic, Manual and Waterflow).
CENTRAL STATION (Automatic, Manual and Waterflow,
and Sprinkler Supervised).
–OT, PSDN (Other Technologies, Packet-switched Data
Network)
FireLite® Alarms and System Sensor® are registered trademarks of
Honeywell International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
SYSTEM SPECIFICATIONS