Installation Instructions and Owner's Manual

10
Installation must be performed by a qualifi ed professional
service technician.
This grill is designed for outdoor use only. DO NOT use this
grill inside a building, garage, or enclosed area. DO NOT use
this grill in or on a recreational vehicle or boat.
When installing this grill in a combustible surround, an RHP
insulating liner must be used.
The grill must have a minimum clearance of 18" from
combustible materials/items in all directions.
OVERHEAD CONSTRUCTION AND EXHAUST
HOOD REQUIREMENTS
A minimum 5 foot clearance is required between the countertop
and the overhead construction.
When installed under combustible overhead construction,
the area above the cooking surface of the grill must be
covered with an exhaust hood. The exhaust hood provides
the protection for the combustible overhead construction.
See exhaust hood information below and Fig. 10-1.
Important: DO NOT use this appliance under unprotected
combustible overhead construction.
When installed under overhead non-combustible construction,
an exhaust hood is highly recommended; see exhaust hood
information below and Fig. 10-1.
Exhaust Hood
When using an exhaust hood, the area above the cooking
surface of the grill must be covered with a hood larger than
the cooking area of the grill, and with a minimum of 1200
CFM (cubic feet per minute) for proper outdoor application.
INSTALLATION REQUIREMENTS
REV 2 - 1611101520
L-C2-435
Fig. 10-1 Overhead requirements
Min.
5'
OVERHEAD CONSTRUCTION
EXHAUST
HOOD
Combustible overhead
construction:
Exhaust hood required
Non-combustible
overhead construction:
Exhaust hood highly recommended