User guide
Configuring Fire Panels
36 198 Pt Addr. Panel
PS-Tools 08/2010
Figure 5-6 Configuring Optional Modules
To configure the optional modules
1. Click EIA-485 Terminal Mode Enabled, to enable the LCD-80F terminal mode annunciator.
This feature allows a series of up to 32 LCD-80F annunciators to be connected to the FACP’s
EIA-485 Terminal Mode connector.
Note If you enable EIA-485 Terminal Mode Enabled (LCD-80) option, then PC/Printer
Installed option in System setup is disabled.
2. Click UDACT-F Communicator Installed, to allow a UDACT-F communicator to connect to
the FACP using the RS-485 ACS connector. If this feature is enabled, the reporting style for the
UDACT-F can be selected between point and zone.
3. Click Annunciators to allow a series of ACS annunciators, to be connected to the RS-485 ACS
connector on the fire panel. If this feature is enabled, each ACS address can be individually
enabled/disabled.
4. Click Save to Database to save the
configuration in the PS-Tools database.
5. Click Next or
click Detectors in SLC Loop Setup in the left pane, to view the SLC Loop
Setup -> Detectors configuration pane.
6. Click Prev to view the General System Settings pane for the 198 Pt Addr. panel.










