User Manual

34 50 Pt Addr Panel
PS-Tools 08/2010
Configuring Fire Panels
Note
If the Canadian option is enabled, then the silence inhibit for NACs becomes a
“global” option. That is, in the panel if you change any NAC to silence inhibit, the
remaining NACs change to silence inhibit. Similarly, if you set any one NAC to
no silence inhibit all the NACs silence inhibit is turned off.
When importing a customer database file f
rom the previous version of PS-Tools,
a check must be performed to ensure whether the Canadian option is enabled. If
the Canadian option is enabled, then the NAC’s silence inhibit must be checked.
If either of them is enabled, then all the NAC’s silence inhibit must be turned off,
and a corresponding message must be displayed to the user.
If Canadian option is ON, then the PAS and Pre-signal timers must b
e set to 0 and
no editing is allowed.
If Canadian option is ON, then
the secondary Ann Bus must be enabled. You can
toggle between the secondary Ann Bus enable and disable option.
Table 5-1
Module types blocked from selection Changes to
Monitor Pull Station
MON User defined 3 Pull Station
Medical Alert, Hazard Alert, and Tornado Alert Supervisory
Supervisory AR (Non-Latching) Supervisory
MON User defined 7, 8, 9, 13, 16, and 17 Supervisory
Drill Switch AR (Non-Latching) Drill Switch
Process Monitor AR and Process Monitor Supervisory
Module and Zone types available for Canadian option
Loop Style
Under Loop Style, select the Loop 1 Style, for the loop. The wiring style can be Style 4 or Style 6.
The default wiring type is Style 4.
Zone types blocked from selection Changes to
AR(auto-resettable) Supervisory Supervisory
Drill Switch AR Drill Switch
Process monitor, hazard, tornado, and medical alert Supervisory