User Manual

PS-Tools User Guide
50 Pt Addr Panel
PS-Tools 08/2010 33
Clock Format
To configure the Clock Format
1. Select the clock format as 24 hours or 12 hours.
a. If you set the 24 Hour Format, the Time is in military format (00:00:00 to 23:59:59) and
the Date is in DD/MM/YYYY format.
b. If you set the 12 Hour Format, the Time is in 12 hours format (AM/PM) and the Date is in
MM/DD/YYYY format (see Figure 5-5).
Trouble Reminder
•Click Trouble Reminder, to enable the trouble reminder option. By default, this option is
disabled.
Water Flow Devices Silenceable
•Click Water Flow Devices Silenceable, to enable the Water Flow Devices Silenceable option.
By default, this option is disabled.
Canadian Option Enabled
To configure Canadian Option
1. Click Canadian Option Enabled.
a. Ensure the input/output zone types are defined as in Table 5-1.
b. You can set the Auto Silence option for NACs, only to No AutoSilence or 20 minutes.
NACs, which are programmed as No AutoSilence, remain in the same mode when
Canadian Option is enabled.
c. If NAC is programmed for Auto Silence, the default time is 20 minutes. If you set the auto
silence time to a value such as 10 or 30 minutes, it is automatically reset to 20 minutes.