Configuring Fire Panels
Configuring Input/Output
The input/output devices include the zones, NACs, and relays. You can configure each relay, zone,
special zone and NACS in the Input/Output Configuration pane.
Figure 5-3 Configuring I
nput/Output
Relay
The fire panel consists of one fixed and two programmable Form-C dry contact relays. The fixed
fail-safe relay monitors the system troubles. The two programmable relays are factory default. By
default, Relay 1 is Alarm, and Relay 3 is Supervisory. They can be programmed for system alarm and
system supervisory, and configured for the following operations;
•Alarm
Supervisory
Supervisory Auto Reset
Trouble
Communication Fail
Process Monitoring
Process Monitoring Auto Reset
•AC loss
Hazard
•Medical
Silenceable Alarm