User guide
53688 8-1
Section 8
Reporting
This section lists receivers that are compatible with this control panel, and the reporting codes
sent by the control panel for SIA and Contact ID formats.
8.1 Receivers Compatible with the Control Panel
Table 8-1 shows receivers compatible with the control panel.
Table 8-1: Receivers Compatible with the Control Panel
8.2 Reporting Formats Dialer Outputs
Manufacturer Model Format
Silent Knight Model 9800 SIA and Contact ID
Model 9000 (SIA formats) SIA
Ademco Model MX8000 (Contact ID) Contact ID
Sur-Gard SG-MLR2-DG (V. 1.64 or higher) SIA and Contact ID
Osborne Hoffman Quickalert SIA and Contact ID
SIA Reporting Format Contact ID Reporting Format
Event Description
Event
Family
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA
Event
Code
Parameter
(if any)
Qualifier
Event
Code
Group
#
Contact
#
System Events
System events are reported when either “Report by Zone” is selected.
AC power restore Trouble System Event AR 3 301 00 000
AC power lost Trouble System Event AT 1 301 00 000
Short circuit removed from SLC communi-
cation loop
Trouble System Event ER 33 3 332 00 Exp. ID
Short circuit detected on SLC communica-
tion loop
Trouble System Event ET 33 1 332 00 Exp. ID
Fire drill has begun Test System Event FI 1 604 00 000
Fire drill ended Test System Event FK 3 604 00 000
Panel date has been changed Trouble System Event JD 1 625 00 000
Panel time has been changed Trouble System Event JT 1 625 00 000
Local programming begin Trouble System Event LB 1 627 00 000