User guide

Programming
53688 6-3
Table 6-2 shows that any input SLC device with an address set within the range 1-15 will be
assigned to zone 1 as an alarm input type. An SLC output relay point assigned to address 111
or 112 will activate for an alarm in zone 1.
6.3.3 Default Mapping for the 2 built-in Notification
Circuits.
There are 2 built-in notification circuits (NAC 1 and NAC 2). They are both defaulted to
activate when any of the 5 zones are in alarm. When active, NAC 1 and NAC 2 will sound the
System Sensor synchronization pattern. To change the behavior of the default mapping of
these circuits refer to Section 6.5.
Table 6-3: Output Points
OUTPUT POINTS
Group Output Point Type Qty
Start SLC
ID
End SLC
ID
Output Activates For
OPG 1 HFS-MR, CRF-300, CRF-300A 2 111 112 Zone 1 Alarm
OPG 2 HFS-MR, CRF-300, CRF-300A 2 113 114 Zone 2 Alarm
OPG 3 HFS-MR, CRF-300, CRF-300A 2 115 116 Zone 3 Alarm
OPG 4 HFS-MR, CRF-300, CRF-300A 2 117 118 Zone 4 Alarm
OPG 5 HFS-MR, CRF-300,CRF-300A 2 119 120 Zone 5 Alarm
OPG 6 HFS-MR, CRF-300, CRF-300A 2 121 122 Zone 1 Supervisory
OPG 7 HFS-MR, CRF-300, CRF-300A 2 123 124 Zone 2 Supervisory
OPG 8 HFS-MR, CRF-300, CRF-300A 2 125 126 Zone 3 Supervisory
OPG 9 HFS-MR, CRF-300, CRF-300A 2 127 128 Zone 4 Supervisory
OPG 10 HFS-MR, CRF-300, CRF-300A 2 129 130 Zone 5 Supervisory
OPG 11 HFS-MR, CRF-300, CRF-300A 2 131 132 Zone 1 Trouble
OPG 12 HFS-MR, CRF-300, CRF-300A 2 133 134 Zone 2 Trouble
OPG 13 HFS-MR, CRF-300, CRF-300A 2 135 136 Zone 3 Trouble
OPG 14 HFS-MR, CRF-300, CRF-300A 2 137 138 Zone 4 Trouble
OPG 15 HFS-MR, CRF-300, CRF-300A 2 139 140 Zone 5 Trouble
OPG 16 HFS-MR, CRF-300, CRF-300A 2 141 142 General Alarm
OPG 17 HFS-MR, CRF-300, CRF-300A 2 143 144 General Supervisory
OPG 18 HFS-MR, CRF-300, CRF-300A 2 145 146 General Zone Trouble
OPG 19 HFS-MR, CRF-300, CRF-300A 2 147 148 General Trouble
OPG 20 HFS-MR, CRF-300, CRF-300A 2 149 150 Alarm Silenced
OPG 21 HFS-MR, CRF-300, CRF-300A 2 151 152 Trouble Silenced
OPG 22 HFS-MR, CRF-300, CRF-300A 2 153 154 AC Loss
OPG 23 HFS-MR, CRF-300, CRF-300A 2 155 156 Resettable Aux Relay
OPG 24 HFS-MR, CRF-300, CRF-300A 2 157 158 Aux Door Holder