User guide

53688 6-1
Section 6
Programming
This section of the manual describes how to change the control panel programming options
from the built-in web page of the control panel. All options described in this section are edited
via the panel’s built in web page
6.1 UL 864 Programming Requirements
*Only needs to be enabled if using the DACT.
Important!
Before any customized programming is done, JumpStart should be run first. After JumpStart
is run, thoroughly test the system. The reason the system should be tested after JumpStart is
because JumpStart automatically programs the system, searching for and configuring all
SLC devices and SBUS annunciators it finds. JumpStart allows you to confirm the integrity
of the installation prior to performing any custom programming. After determining that the
hardware is properly installed, custom programming can be performed. Refer to Section 6.
Table 6-1: Standards in Requirements for Control Units and Accessories
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES: This product incorporates field programmable software. In
order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Programming Option Menu Item
Permitted in
UL 864 (Y/N)
Possible
Settings
Settings Permitted in
UL 864
System Options Low AC Report Delay Yes 0–30 hours 1–3
Zone Options Supervisory Yes Latching/Non Latching
Zone Options Waterflow Yes Latching/Non Latching
System Options Alarm Verification Yes 1-250 seconds 60-250 seconds
Dialer Phone line Programming
option
Line Monitor Enabled Yes Y/N Y*