Before You Begin Installing
This section of the manual is intended to help you plan your tasks to facilitate a smooth
installation. Please read this section thoroughly, especially if you are installing a MS-25 panel
for the first time.
3.1 What’s in the Box?
The MS-25 ships with the following hardware:
A cabinet with all hardware assembled
Two keys for the front door
Installation and Operation manual P/N 53688
Ten 4.7K ohm end-of-line resistors
A battery cable for batteries wired in series
3.2 Environmental Specifications
It is important to protect the MS-25 control panel from water. To prevent water damage, the
following conditions should be AVOIDED when installing the units:
Intended for indoor use in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)
When selecting a location to mount the MS-25 control panel, the unit should be mounted
where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or
humidity outside the range of 10%-93% at 30°C (86°F) noncondensing.