24 Viceroy Road Unit #6 & 7 Concord, Ontario L4K2L9 Phone (905) 660-7210 FAX: (905) 660-7204 MS-2410BC Conventional Fire Alarm Control Panel Programming, Installation, Maintenance and Operating Instruction Manual Document 12/14/01 #50801 Rev.
Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized.
Notes 4 Document #50801 Rev.
Table of Contents CHAPTER 1: Product Description ......................................................................................................................... 9 1.1: Product Features ..........................................................................................................................................9 FIGURE 1-1: DP-2410BC ...................................................................................................................9 FIGURE 1-2: MS-2410BC Panel .........
Table of Contents 3.3: Entering Program Mode ..............................................................................................................................34 FIGURE 3-2: Programming Security Key - Program Mode ...............................................................34 3.4: Programming Function................................................................................................................................34 3.4.1: Program Feature Selection ..............................
This control panel has been designed to comply with standards set forth by the following regulatory agencies: Before proceeding, the installer should be familiar with the following documents. NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards: NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems (Automatic, Manual, Waterflow and Sprinkler Supervisory) and Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems.
MS-2410BC Main Circuit Board AC Power MS-2410BC Terminals and Connectors 8 Document #50801 Rev.
Product Description CHAPTER 1 Product Description The MS-2410BC is a 10-zone FACP (Fire Alarm Control Panel), which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally-open contact devices. Outputs include two Notification Appliance Circuits (NACs), three standard Form-C relays (alarm, trouble and supervisory) and an EIA-485 port to interface with remote annunciators and optional remote relay modules.
Product Features FIGURE 1-2: MS-2410BC Panel 24 VDC Power Notification Appliance Circuits Remote Trouble Buzzer 10 Input Zones Security Key Relays Standard Transformer LED-10IM Interface Module Connector Keypad and LEDs Reverse Polarity Module Optional Transformer Reverse Polarity Module Supervision Holds up to 7 AH Batteries, 10 Document #50801 Rev.
Specifications 1.2 Specifications AC Power - TB1 120 VAC, 60 Hz, 2.3 amps Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation Battery (lead acid only) - J1 Maximum Charging Circuit: Normal Flat Charge—27.6V @ 0.8 amp Maximum Charger Capacity: 18 Amp Hour battery (MS-2410BC cabinet holds maximum 7 Amp Hour battery.
Controls and Indicators Nonresettable 24 VDC Power - TB2 Terminals 1(-) & 2(+) Maximum ripple voltage: 10 mVRMS Operating Voltage nominal 24 volts Total DC current available from this output is up to 500 mA 1 Recommended maximum Standby current is 150 mA Refer to Fire•Lite Device Compatibility Chart for compatible listed devices Remote Trouble Buzzer - TB5 Operating Voltage: nominal 24 VDC DC current when RTB Remote Trouble Buzzer is in normal standby (AC Power LED on alone) is 20 mA.
Circuits Local Sounder A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions: • Alarm - on steady • Alarm Verification - pulse 1 second On and 1 second Off • Trouble - pulse 1 second On and 1 second Off • Supervisory - pulse ½ second On and ½ second OFF 1.4 Circuits Input Circuits Ten input circuits provide Class B configuration.
Optional Modules Cabinet The cabinet is red and the backbox measures 20.00" (50.8 cm) long X 17.00" (43.18 cm) high X 3.125"(7.938 cm) deep and provides space for two batteries (up to 7 Amp Hours). Also included is a dress panel, DP-2410BC, which comes premounted inside the cabinet. FIGURE 1-5: MS-2410BC Cabinet Transformer Assembly One 100VA transformer is provided standard with the panel. An optional 100VA transformer, XRM-24, is available to provide maximum accessory power.
Optional Accessories Battery Box The Fire•Lite BB-17F battery box may be used to house two batteries greater than 7 Amp Hour to a maximum of 18 Amp Hour. The battery box mounts directly below the MS-2410BC cabinet, centered to the main circuit board. The BB-17F is red and is provided with knockouts. FIGURE 1-7: BB-17F Battery Box Remote Trouble Buzzer One Remote Trouble Buzzer can be connected to the MS-2410BC control panel using four wires.
Optional Accessories AFM Series Annunciators (LED Zone Type) The AFM Series Annunciators remotely display system status. The AFM/AEM-16AT annunciators display zone alarm and trouble status. In addition, they provide remote Acknowledge, Silence, Reset and Drill functions. The AFM Series Annunciators require the use of the LED-10IM Interface Module. For more detailed information, refer to the appropriate AFM Annunciator manual.
Optional Accessories LDM Series Lamp Driver Modules (Graphic Annunciator) The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic LED annunciator. The master module provides power and control for a maximum of three expander modules (expander modules are not required when interfacing to the MS-2410BC).
Optional Accessories One of the most common applications for the FCPS-24F remote power supply utilizes the NAC expander mode. In this application, one or two Notification Appliance Circuits (NACs) are connected from the main FACP NAC output(s) to the remote power supply Control Input circuits. When these Control Input circuits activate (due to reverse polarity of the NAC output), the power supply will activate its corresponding outputs. NAC Control Input #1 controls power supply output circuits #1 and #2.
Installation CHAPTER 2 2.1 Installation Mounting Options FIGURE 2-1: MS-2410BC Mounting The cabinet may be either semi-flush or surface mounted. The door is attached to the cabinet by a piano hinge. The cabinet mounts using two key slots and two additional 0.250" (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom. Carefully unpack the system and check for shipping damage.
Backbox Mounting Draw wires through the respective knockout locations. FIGURE 2-2: Cabinet Dimensions and Knockout Locations Top Right Side Left Side Bottom 20 Document #50801 Rev.
Backbox Mounting FIGURE 2-3: FACP Backbox When batteries larger than 7 Amp Hour are being used, the BB-17F battery box (or equivalent) must be installed. To install the BB-17F: 1. 2. 3. 4. Mount the FACP cabinet to the wall. Remove knockouts on the bottom of the FACP cabinet and top of the BB-17F. Using conduit, hang the BB-17F from the FACP cabinet making sure there is at least ½" of clearance between the two cabinets. Anchor the BB-17F to the wall. Document #50801 Rev.
Operating Power 2.3 ! Operating Power WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized. Primary Power Source (AC) and Earth Ground Connections AC power connections are made inside the control panel cabinet. The primary power source for the MS-2410BC is 120 VAC, 60 Hz, 2.3 amps.
Input Circuits 2.4 Input Circuits The control panel has 10 zone input circuits. The maximum loop resistance limit for each input circuit is 100 ohms. All field wiring of each zone is supervised for opens and ground faults. Both conditions are visually and audibly annunciated. Each zone is a Class B Initiating Device Circuit (IDC) designed to accept any normally-open contact devices and conventional 2-wire, 24 volt smoke detectors. All zones may be configured for general fire alarm applications.
Output Circuits 2.5 Output Circuits DC Power Output Connections . FIGURE 2-6: Auxiliary Power Connections Nonresettable Power (500 mA) 24 VDC filtered, nonresettable power can be obtained from TB2 Terminals 1(-) and 2(+). 4-Wire Smoke Detector Power (500 mA) 24 VDC filtered, resettable power for 4-wire smoke detectors can be obtained from TB2 Terminals 3(-) and 4(+) 4 3 2 1 Notification Appliance Circuits The MS-2410BC provides two Notification Appliance Circuits standard as Class B.
Power-limited Wiring Requirements Standard Relays The control panel provides three Form-C relays rated for 2.0 amps @ 30 VDC (resistive) and 2.0 amps @ 30 VAC (resistive). FIGURE 2-8: Relay Terminals Relay connections may be power-limited or nonpower-limited, provided that a minimum of 0.25" is maintained between conductors of power-limited and nonpower-limited circuits.
Installation of Optional Modules with Remote Accessories 2.7 ! Installation of Optional Modules with Remote Accessories CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring. RTB - Remote Trouble Buzzer The RTB is a Remote Trouble Buzzer which provides a green AC Power LED and a yellow Trouble LED along with a piezo sounder, all of which mimic the condition of the control panel. The RTB can be mounted remotely in a single-gang electrical box.
Installation of Optional Modules with Remote Accessories CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring. ! LED-10IM - EIA-485 Interface Module The LED-10IM Interface Module provides an EIA-485 port to support the LED-10 Series Remote Annunciator, LDM Series Annunciator, AFM Series Annunciator and the ACM-8RF Relay Module. EIA-485 wiring is supervised for open circuits by this module. The LED-10IM mounts to connector J5 on the MS-2410BC main board.
Installation of Optional Modules with Remote Accessories ! CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring. ACM-8RF Remote Relay Module FIGURE 2-13:ABS-8RF The ACM-8RF Module provides eight Form-C relays with contacts rated for 5.0 amps. Relays can be assigned to each of the ten Initiating Device Circuits (two ACM-8RF relay modules are required). The module is installed on the EIA-485 line using the LED-10IM Interface Module.
Installation of Optional Modules with Remote Accessories ! CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring. LDM-32F Lamp Driver Module The Lamp Driver Module is used to provide an interface to a custom graphic annunciator. The LDM-32F has 32 alarm lamp/LED driver outputs which sink current to system common (-) on activation. A single positive (+) voltage is required to supply total operating power for all lamps or LEDs when all drivers are activated.
Installation of Optional Modules with Remote Accessories ! CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring. AFM-16ATX and AFM-16ATF Annunciators The Annunciator Fixed Modules-16ATX and 16ATF each contain 16 red alarm and 16 yellow trouble LEDs, a system trouble LED, an ON LINE/POWER LED and a local piezo sounder with switches for FACP Acknowledge, Silence, Reset and Drill.
Installation of Optional Modules with Remote Accessories ! CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring. 4XTMF Transmitter Module Push the disconnect switch to the down position to prevent accidental activation of the municipal box during testing of the control panel. The Disconnect LED will remain illuminated while the municipal box is disconnected. The System Trouble LED will indicate disconnected and/or open circuit conditions on the municipal box.
Programming Instructions CHAPTER 3 Programming Instructions This chapter describes programming the MS-2410BC from the onboard keypad. Programming can be performed only by a factory authorized representative. Control panel programming is possible at any time except when an alarm or zone fault condition is present or during a fire drill. All programming selections are stored in nonvolatile Electrically-Erasable Programmable Read-Only Memory (EEPROM).
Programmable Features and Options 3.2 Programmable Features and Options Table 3-1 lists the MS-2410BC programmable features and the corresponding options available for each feature. In programming mode, the zone alarm LEDs are used to 'point' to the program feature and the zone trouble LEDs are used to select the desired option for each feature.
Entering Program Mode 3.3 Entering Program Mode The keypad is enabled, to allow switching from Normal Mode to any other mode, by inserting the Security Key into connector J4 on the MS-2410BC main circuit board. FIGURE 3-2: Programming Security Key - Program Mode Security Key P/N: PKB MS-2410BC Insertion of the Security Key alters the functions of the keypad. Keys labeled 1 through 4 may now be used for entering a numerical password.
Programming Function is on steady, acts as a 'pointer', indicating the control panel feature that will be programmed. The blinking zone trouble LED acts as a 'cursor', indicating the option for the currently selected program feature. The Up and Down arrow keys can be used to position the 'cursor' at any Zone trouble LED. 3.4.1 Program Feature Selection Position the 'pointer' at the zone alarm LED, corresponding to the program feature that is to be changed, by pressing the Enter key.
Programming Function 2. Using the numerical keys, enter the Program Mode password and press the Enter key F O Trouble Supervisory Signal Silence NAC Fault Password Ground Fault Battery Trouble Zone Disabled Enter Annunc. Trouble 3. 4. The 'pointer' will be located at the Zone 1 alarm LED which will be on steady. The 'cursor' will be located at the Zone 1 trouble LED which will blink and one or more additional zone trouble LEDs may be on steady Zone 1 Alarm LED Zone 1 Trouble LED 5. 6.
Programming Function 7. Press the keypad 3 key (Toggle Option) to select the auto-resettable option. Repeated pressing of the 3 key will toggle between the two available options. Note that in this option, latching is either enabled or disabled. If latching is disabled, the autoresettable option is automatically selected. Since latching is disabled, the 'cursor' will blink at a 1/10 second On and 9/10 second Off rate. The LED will turn off when the cursor is moved off of it.
Programming Function 10.Press the Down arrow key to position the 'cursor' at the Zone 3 trouble LED which corresponds to the Zone 9 Smoke/Supervisory option. Refer to Table 3-6, “Supervisory Alarm - Zone 4 Alarm LED,” on page 41 11.Press the keypad 3 key (Toggle Option) to select the Supervisory option. The cursor should blink at a 1/10 second On and 9/10 second Off rate. The LED will turn off when the cursor is moved off of it. Note that in this option, supervisory is either enabled or disabled.
Program Features and Options 14.Press the Down arrow key to position the 'cursor' at the Zone 5 trouble LED which corresponds to the Canadian Supervisory option. Refer to Table 3-6, “Supervisory Alarm - Zone 4 Alarm LED,” on page 41 15.Press the keypad 3 key (Toggle Option) to disable the Canadian Supervisory option. The cursor should blink at a 1/10 second On and 9/10 second Off rate.
Program Features and Options Auto-silence Auto-silence is the program feature that will automatically silence the Notification Appliance Circuits, if they are programmed as silenceable circuits, after a programmed time interval. The factory default setting is auto-silence disabled. Note that one and only one of the four selections must be selected or the panel will not allow the programmer to continue.
Program Features and Options The Canadian Supervisory option functions in the same manner as the non Canadian Supervisory option except the zone's supervisory alarm LED is yellow.
Program Features and Options AC Loss Delay When AC power is lost or a brownout condition occurs (AC voltage drops below a predetermined level), the control panel trouble relay will activate. The factory default option for this feature is immediate trouble relay activation on AC loss or brownout. Relay activation may be delayed by selecting one of the seven available time delays as listed in the following table.
Program Features and Options LDMs, LED-10 series and ACM-8RFs, be certain that none of the other devices are set to address 01. For proper supervision of all annunciators, only one AFM series annunciator (fixed at address '01') should be installed.
Default Programming Mode 3.6 Default Programming Mode The original factory default options can be programmed into the MS-2410BC by entering Default Programming Mode. The keypad is enabled, to allow switching from Normal Mode, by inserting the Security Key into connector J4 on the MS-2410BC main circuit board. FIGURE 3-4: Programming Security Key - Default Programming Mode Security Key P/N: PKB MS-2410BC Insertion of the Security Key alters the functions of the keypad.
Operating Instructions CHAPTER 4 Operating Instructions FIGURE 4-1: LED Indicators and Keypad The MS-2410BC has five modes of operation which are Normal, Program, Walktest, Last Event (History) and Default. There are also two function modes: Zone Disable/Enable and Drill. Upon initial power-up, the system will be in Normal Mode. This section discusses operation of the control panel in the Normal Mode. 4.
Status LEDs Disable/Enable The zone disable feature may be used to disable any zone in the system. Zones in alarm cannot be disabled but zones in trouble can be disabled. To disable one or more zones, press and hold the Disable/Enable key. After two seconds, the FACP will enter Disable/Enable Mode. Continue pressing the Disable/Enable key to remain in this mode. Fire protection is still active while in this mode. Releasing the key will return the FACP to Normal Mode.
Operation Supervisory LED (Zones 9 and 10 Only) A yellow LED that blinks to indicate the need for action in connection with the supervision or maintenance of sprinklers, extinguishing systems or other protective systems. It turns on steady when a Signal Silence or Acknowledge key is pressed. Signal Silence LED A yellow LED that turns on to indicate that an Alarm condition exists in the system, but Notification Appliance Circuits (if programmed as silenceable) and local piezo sounder have been silenced.
Operation Higher priority events take precedence over lower priority events. Display and reporting of System Status is done on a priority basis. Priorities are, from highest to lowest: 1. 2. 3. Alarms Supervisory Alarms System Troubles 4.3.
Operation • Turn on supervisory relay • Blink all remote annunciator general supervisory alarm LEDs (½ second On, ½ second Off) • Blink all remote annunciator zone supervisory alarm LEDs (½ second On, ½ second Off) 4.3.
Servicing CHAPTER 5 5.1 Servicing Walktest Mode The MS-2410BC provides the capability to perform a walktest of the system without triggering the ACM-8RF zone relays, the system annunciators or the alarm output relay. Walktest Mode allows for testing of the 10 zones (initiating device circuits). An audible or silent walktest may be performed. For an audible walktest, the first initiating device activated on a zone will cause the Notification Appliance Circuits to turn on for four seconds.
Last Event/History Mode • Display all alarm conditions as they occur • Display all zone troubles as they occur • Display all system troubles as they occur All zone alarm LEDs that turned on during Walktest remain on until the Reset key is pressed. Note that disabled zones will not respond during the Walktest. A zone may be disabled while in Walktest Mode. Should a faulty device require repair, the zone may be disabled while the repair is performed.
Lamp Test conditions on the FACP have changed since the last panel activation. Table 5-1 lists possible panel activations and the LEDs which will be on for each in Last Event/History Mode.
Battery Calculations Battery Calculations Appendix A Use the Total Standby and Alarm Load Currents calculated in Table A-2 and Table A-3 for the following battery calculation. TABLE A-1: Battery Calculation Standby Load Current (amps) [ X ] [ Alarm Load Current (amps) [ ] Required Standby Time in Hours (24 or 60 Hours) X Required Alarm Time in Hours (i.e. 5 min. = 0.084 hours) [ = _______________ = _______________ = _______________ X 1.
Battery Calculations A.1 Main Power Supply The MS-2410BC provides filtered power for operating the fire alarm control panel, operating external devices and operating the standby battery. The power for operating external devices is limited. Use Table A-2 (standby or nonalarm) and Table A-3 (alarm) to determine if external loading is within the capabilities of the power supply. Be certain to power 4-wire smoke detectors from TB2, Terminals 3 and 4. In Table A-2 , external devices are connected to TB2 only.
Battery Calculations TABLE A-3: Filtered Load in Alarm @24 VDC . Device Type # of Devices Main Circuit Board 1 X 0.245 = RTB Remote Trouble Buzzer (1 max.) X 0.050 = LED-10IM (1 max.) X 0.017 = X 0.0112 = 4XTMF Module (1 max.) Current (amps) Total Current (amps) 4-wire Smoke Detector3 [ ] X [ ] = Power Supervision Relay4 [ ] X 0.025 = Notification Appliances5 [ ] X [ ] = Notification Appliances [ ] x [ ] = Current Draw from TB23 (alarm current) 0.
Wire Requirements Appendix B Wire Requirements Connecting external system accessories to the MS-2410BC main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, wire gauge and wire run length per each MS-2410BC circuit. Reference the chart below to specify wire requirements and limitations for each MS-2410BC.
Slide-in Labels Appendix C Slide-in Labels The spare slide-in labels on the following pages are provided for the MS-2410BC keypad and display panel in the event that the original labels are lost or damaged. The labels may be cut from the manual or photo-copied and then carefully cut out and inserted into the proper location, as indicated in Figure C-1. Labels slide into pockets which are accessible through the top of the keypad and display panel.
Slide-in Labels 58 Document #50801 Rev.
Slide-in Labels Normal Mode Slide-in Labels Type appropriate information on blank Label A prior to cutting from page. Typed entries must be centered and typed on the lines provided to ensure proper positioning in the membrane windows. Be certain to cut labels directly on dotted lines to ensure proper fit.
Slide-in Labels 60 Document #50801 Rev.
Slide-in Labels Program Mode Slide-in Labels Be certain to cut labels directly on dotted lines to ensure proper fit F O Label A - Program Mode Label C - Program Mode Auto Silence Silenceable NACs Walk Test 1 Supervisory Alarm Alarm Verification 2 AC Loss Delay Module Supervision Annunc.
Slide-in Labels 62 Document #50801 Rev.
Limited Warranty The manufacturer warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service.
World Headquarters One Fire-Lite Place, Northford, CT 06472-1653 USA 203-484-7161 • Fax 203-484-7118 www.firelite.