Manual
58 411UDAC Manual — P/N 51073:E 9/20/2013
Central Station Communications Ademco Contact ID Format Event Code Description
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble
reports in the Ademco Contact ID Reporting Structure follows:
Time Date Rcvr/Line ID SSSS QXYZ GG CCCC
11:28 03/25 11 7777 E110 00 C001 - general fire alarm on Channel/Input 1
11:28 03/25 11 7777 E111 00 C002 - smoke detector alarm on Channel/Input 2
11:28 03/25 11 7777 E380 00 C003 - fault on Channel/Input 3
11:28 03/25 11 7777 R110 00 C001 - Channel/Input 1 alarm restored
11:28 03/25 11 7777 R111 00 C002 - smoke detector Channel/Input 2 restored
11:28 03/25 11 7777 R380 00 C003 - Channel/Input 3 fault restored
11:28 03/25 11 7777 E158 00 C004 - high temperature, Channel/Input 4
11:28 03/25 11 7777 E151 00 C004 - gas detected, Channel/Input 4