Transmittal Priorities Central Station Communications
4.1 Transmittal Priorities
The digital communicator transmits highest priority events first. Events in terms of priority are
listed below in descending order:
1. Fire Alarm (highest priority level)
2. Fire Supervisory
3. System Troubles
Host Panel Trouble (active input programmed for trouble)
AC Fail (after delay)
Channel/Input faults
Telephone line fault
Communication trouble
System Off Normal
4. Restoral Reports
Fire Alarm
Fire Supervisory
Host Panel Trouble
–AC
Channel/Input fault
Telephone line
Communication
System Off Normal
5. System Test
6. Upload/Download events (lowest priority)
4.2 Ademco Contact ID Format Event Code Description
This section describes the various Event Codes and their messages which are available for the
Ademco Contact ID Format. The reporting structure for the Ademco Contact ID Format is as fol-
lows:
SSSS 18 QXYZ GG CCC
Notes:
1. 18
, which is used in the reporting structure to identify the transmission as Contact ID, is not
printed out in the alarm and trouble report.
2. Q
, which is the Event Qualifier for the reporting structure, is printed out in the report as an E
for New Event or R
for New Restore.
3. GG Group Number is fixed at '00' and cannot be changed.
4. CCC Channel/Input Number is transmitted as '001' for Channel/Input 1, '002' for
Channel/Input 2, '003' for Channel/Input 3, '004' for Channel/Input 4.
Where:
SSSS = Four digit Subscriber ID Account Code (addresses 21 - 24 and 51 - 54)
18 = Identifies transmission as Contact ID to the receiver at the Central Station
Q = Event Qualifier where 1 = New Event and 3 = New Restore
XYZ = Event code (shown in Tables)
GG = Group number
CCC = Channel/Input number