Central Station Communications
The digital communicator is capable of reporting detailed messages depending upon the Format in
use. Table 4.1 shows the data reporting structure for each of the pulsed formats as well as the
Ademco Express Formats. Ademco Express Formats allow a typical data message to be transmit-
ted to the Central Station in under 5 seconds. Pulsed formats typically require 15 to 20 seconds in
comparison. Table 4.2 defines each letter code used in Table 4.1 . See “Ademco Contact ID For-
mat Event Code Description” on page 57 for a description of the data reporting structure for
Ademco Contact ID Format.
Format #
0, 2, 4, 6, 8
Format #
3, 5, 7, 9
Format #
1, A, C
Format #
B, D
Report 3+1/4+1/Standard
4+1 Express
3+1/4+1/Expanded 4+2/Standard 4+2
Express
4+2/Expanded
Fire Alarm SSS(S) FA SSS(S) FA
FAFAFA(FA) 2
SSSS FAFA2 SSSS FAZ
Fire Alarm Restore SSS(S) RFA SSS(S) RFA
RFARFARFA (RFA) 2
SSSS RFARFA2 SSSS RFAZ
Channel/Input Trouble
(Channel/Input Open)
SSS(S) TZ SSS(S) TZ
TZTZTZ(TZ) Z
SSSS TZTZ2 SSSS TZZ
Channel/Input Trouble Restore SSS(S) RTZ SSS(S) RTZ
RTZRTZRTZ(RTZ) Z
SSSS RTZRTZ2 SSSS RTZZ
System Trouble SSS(S) TS SSS(S) TS
TSTSTS(TS) Y
SSSS TSTS2 SSSS TSY
System Trouble Restore SSS(S) RTS SSS(S) RTS
RTSRTSRTS(RTS) Y
SSSS RTSRTS2 SSSS RTSY
AC Loss SSS(S) P SSS(S) P
PPP(P) Z
SSSS PP2 SSSS PP2
AC Loss Restore SSS(S) RP SSS(S) RP
RPRPRP(RP) Z
SSSS RPRP2 SSSS RPRP2
Fire Supervisory Condition SSS(S) V SSS(S) V
VVV(V) Z
SSSS VV2 SSSS VZ
Fire Supervisory Condition
Restore
SSS(S) RV SSS(S) RV
RVRVR(RV) Z
SSSS RVRV2 SSSS RVZ
Test Report SSS(S) X SSS(S) X SSSS XX2 SSSS XX2
Up or Download SSS(S) UD SSS(S) UD SSS UDUD2 SSS UDUD2
Table 4.1 Format Selection Addresses (20 and 50) Programming