Manual

40 411UDAC Manual — P/N 51073:E 9/20/2013
Modes of Operation Program Mode
Primary Central Station Number Account Code (21 - 24)
The four locations at addresses 21 - 24 default to all '0's. Valid entries are 0 - 9 and A - F. The num-
ber of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 20,
enter three digits (one digit each in locations 21, 22 and 23 - location 24 is ignored). If program-
ming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into address 20, enter four digits (one each in locations 21, 22,
23 and 24).
Primary Central Station Number 24 Hour Test Time (25 - 28)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1
takes up four locations, from addresses 25 - 28. The default is 00:00 (12:00 midnight). The limits
for each location are as follows (do not use values of A - F as entries).
25: enter 0, 1 or 2
26: enter 0 - 9
27: enter 0 - 5
28: enter 0 - 9
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (29)
The test report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the
message is to be sent every 24 hours, leave the factory default entry of '0'. If other test report times
are needed, enter 1 = 12 hour, 2 = 8 hour or 3 = 6 hour.
Secondary Central Station Phone Number (30 - 49)
Addresses 30 - 49 are factory set to 'F' (30_F to 49_F). Programming is typically done as follows:
If your phone number is 484-7161, press 4.
The display will read 30_4.
Press [ENTER/STORE] to save the entry to memory and increment to the next address
31_F.
171 Primary # Input Channel 4 Fault Restore Code D
172 Primary # AC Voltage Fault Restore Code 9
173 Primary # Earth Fault Restore Code A
174 Primary # Low Battery Fault Restore Code A
175 Primary # No Battery Fault Restore Code A
176 Primary # Phone Line 1 Voltage Fault Restore Code A
177 Primary # Phone Line 2 Voltage Fault Restore Code A
178 Primary # NAC Fault Restore Code A
179 Primary # Charger Fault Restore Code
180 Primary # Phone Number 1 Communication Fault Restore Code A
181 Primary # Phone Number 2 Communication Fault Restore Code A
182 Primary # System Off Normal Restore Code A
183 Primary # System Test Message 9
184 Primary # System Abnormal Test Message F
*
185 Primary # Upload/Download Request Code 7
186 Primary # Upload Successful Code 7
187 Primary # Download Successful Code 7
188 Primary # Upload/Download Failed Code 7
* For Formats ‘B’ and ‘D’, this address is defaulted to ‘9’ instead of ‘F.’
Address Description Setting