Manual

38 411UDAC Manual — P/N 51073:E 9/20/2013
Modes of Operation Program Mode
4+2 Standard and 4+2 Express Formats Primary Central Station Event Codes
If ā€˜1, A or C’ is entered for address 20, the following data is automatically programmed for the Pri-
mary Central Station phone number event codes. Enter '00' for the Setting to disable the report to
the Central Station.
175 -177 Primary # Low Battery Fault Event Code 302 000
178 - 180 Primary # No Battery Fault Event Code 311 000
181 - 183 Primary # Phone Line 1 Voltage Fault Event Code 351 000
184 - 186 Primary # Phone Line 2 Voltage Fault Event Code 352 000
187 - 189 Primary # NAC Fault Event Code 321 000
190 - 192 Primary # Charger Fault Event Code 300 000
193 - 195 Primary # Phone Number 1 Communication Fault Event Code 354 001
196 - 198 Primary # Phone Number 2 Communication Fault Event Code 354 002
199 - 201 Primary # System Off Normal Fault Event Code 308 000
202 - 204 Primary # System Test Message 602 000
205 - 207 Primary # System Abnormal Test Message 608 000
208 - 210 Primary # Upload/Download Request Code 411 000
211 - 213 Primary # Upload Successful Code 416 000
214 - 216 Primary # Download Successful Code 412 000
217 - 219 Primary # Upload/Download Failed Code 413 000
Address
Description Setting Channel/Input #
Table 3.1 Ademco Contact ID Format - Primary
Address Description Setting
145 - 146 Primary # Input Channel 1 Active Event Code 11
147 - 148 Primary # Input Channel 2 Active Event Code 12
149 - 150 Primary # Input Channel 3 Active Event Code 13
151 - 152 Primary # Input Channel 4 Active Event Code 14
153 - 154 Primary # Input Channel 1 Fault Event Code F1
155 - 156 Primary # Input Channel 2 Fault Event Code F2
157 - 158 Primary # Input Channel 3 Fault Event Code F3
159 - 160 Primary # Input Channel 4 Fault Event Code F4
161 - 162 Primary # AC Fault Event Code 92
163 - 164 Primary # Earth Fault Event Code 61
165 - 166 Primary # Low Battery Fault Event Code 62
167 - 168 Primary # No Battery Fault Event Code 63
169 - 170 Primary # Phone Line 1 Voltage Fault Event Code 64
171 - 172 Primary # Phone Line 2 Voltage Fault Event Code 65
173 - 174 Primary # NAC Fault Event Code 66
175 - 176 Primary # Charger Fault Event Code 47
177 - 178 Primary # Phone Number 1 Communication Fault Event Code 6A
179 - 180 Primary # Phone Number 2 Communication Fault Event Code 6B
181 - 182 Primary # System Off Normal Fault Event Code 6F
183 - 184 Primary # Input Channel 1 Active Restore Code E1
185 - 186 Primary # Input Channel 2 Active Restore Code E2
187 - 188 Primary # Input Channel 3 Active Restore Code E3
189 - 190 Primary # Input Channel 4 Active Restore Code E4
191 - 192 Primary # Input Channel 1 Fault Restore Code D1
193 - 194 Primary # Input Channel 2 Fault Restore Code D2
195 - 196 Primary # Input Channel 3 Fault Restore Code D3
Table 3.2 4+2 Standard and 4+2 Express Formats - Primary