26 411UDAC Manual — P/N 51073:E 9/20/2013
Installation Output Circuits
Relay Programming
The relays are programmable for activation on fire alarm, host panel trouble, fire supervisory, total
communication failure and DACT. Refer to “DACT Programming” on page 36. Addresses ‘85 -
88’ are used for programming relay functions and enable.
RELAY 1 RELAY 2
TB1
NO NONC NCCC
Figure 2.8 Programmable Relay
Note: Relay connections may be power-limited or nonpower-limited. However, connecting one type next to the
other type is not allowed. Both circuits must be either power-limited or nonpower-limited.
Relays automatically change to energized
condition when programmed for Trouble.
411arele.wmf
Relay 1 - Shown Programmed for Alarm,
Supervisory, or any other function except
DACT Trouble and Host Panel Trouble
(relay contacts shown in de-energized
condition with power applied to 411UDAC)
Relay 2 - Shown Programmed for
DACT Trouble or Host Panel
Trouble (relay contacts shown in
energized condition with power
applied to 411UDAC)