Section 1: Product Description
The 411UDAC is a fire alarm communicator with four input/channels and dual telephone lines.
The four inputs use conventional input devices. The 411UDAC accepts waterflow devices, four-
wire smoke detectors, pull stations and other normally-open contact devices. The unit also super-
vises AC voltage, telephone line input voltage/current, battery level and battery charger operation.
Outputs include one supplementary NAC (Notification Appliance Circuit), two programmable
Form-C relays and 12 VDC resettable special application power. The 411UDAC interfaces with
the public switched telephone network and is compatible with most central station receivers. A
total of fifteen popular communications formats are supported, including the industry standard
Ademco Contact ID. The communicator also contains a unique DACT option that eliminates
'dialer runaway'. It restricts the transmission of any intermittent nuisance fault to 10 attempts in a
24 hour period.
Accessories include the Fire-Watch 411 Series DACT Programmer (Model PRO-411) as well as the
PK-411UD Windows
®
-based remote site programming software. The 411UDAC is supplied with
a compact metal cabinet.
The digital communicator can be programmed or interrogated off-site via the public switched tele-
phone network. Any IBM compatible personal computer with Windows
®
XP or greater, with a
1200 baud Hayes
®
compatible modem and Upload/Download software P/N PK-411UD, may serve
as a service terminal.
1.1 Product Features
Four input/channels - three fixed Style B (Class B) and
one Style A (Class A) or Style B (Class B)
Programmable input channels
4-wire smoke (Inputs 1 & 3 only)
pull station
normally-open contact
host panel trouble (Slave Mode)
supervisory
supervisory autoresettable
waterflow (silenceable)
waterflow (nonsilenceable)
One Style Y (Class B) NAC (supplementary application)
Dual telephone lines
Dual telephone line voltage detect
Alternating phone lines for 24 hour test messages
12 VDC operation
Alarm Verification
Signal Silence Inhibit
Autosilence
Trouble Reminder
Trouble Resound - troubles will resound the buzzer every 24 hours at midnight until the
trouble is cleared
Optional TR-6 Series Trim Ring
20-digit central station and service terminal telephone numbers
NAC coding per ANSI S-3.41 (Temporal Coding)
Figure 1.1 411UDAC Digital
Communicator