Users Manual
Commissioning
Commissioning FCR012
Figure: RF ports and Power Cable Glands location
Connection step by step
Connection FCR012
A. RF Ports: Connect the service antennas to the To Mobile Port and each PS700
and PS800 donor antennas to the To Base RF Ports. N type female connectors are
used in this Signal Booster.
B. Once the RF ports of the Signal Booster are properly loaded connect the Main
AC power. If using the AC model, electrical installation must provide differential
and thermo-magnetic breaker elements according to electric safety international
regulations.
C. Make sure that not used cable glands are properly sealed. For this, use the seal plug and
self-amalgamating tape.
D. Auxiliary DC connection can be provided to the device from an external DC source. There
is a dedicated port for this purpose, and a dedicated DC connector labelled “VDC IN” located
inside the cabinet. Please check appropriate DC voltage at Signal Booster specification sheet.
E. NFPA Dry Contacts: there is a dedicated cable gland for this purpose. A multi-
conductor cable can be used to connect the NFPA dry contacts to the Fire
Department Control Box.