Drum Pump Flow Meter Model FMBC2000 Series Operating Instructions
Table of Contents Safety 1 Introduction......................................................................................................................................................... 1 Specificatons...................................................................................................................................................... 1 Features..............................................................................................................................................
Safety ALWAYS wear protective clothing, eye protection and follow standard safety procedures when handling corrosive or personally harmful materials. NEVER use this flow meter with flammable or combustible liquids. NEVER use this flow meter in a hazardous environment. ALWAYS verify chemical compatibility with the flow meter and pump materials of construction before operation. ALWAYS make sure the pump and hose are properly supported.
Section 1 - Installation WARNING: While wiring the meter, make sure all power is disconnected. NOTE: Avoid exposing the LCD for prolonged periods to direct sunlight or the life of the LCD may be reduced.
Front Panel Display Main Menu (not programming mode menu) Pressing the button cycles through the main menu screens. • First screen is “Rate” – this displays actual flow rate of the liquid passing through the meter (either gallons per minute or liters per minute depending upon meter. • Second screen is “Total” – this displays the total volume of liquid that has passed through the meter. This total will continue to accumulate until the button is pressed and the total is reset to zero.
Calibration While the FMBC-2000 has been calibrated at the factory, field calibration is possible to increase accuracy at a given flow. Use the flowing steps for field calibration. NOTE: If the Front Panel Programming has been disabled, the meter cannot be calibrated until the Front Panel Programming has been re-enabled. See “Disabling Front Panel Programming” Section.
Step Four – Calculate new Total Scale Factor For gallons per minute Note: Factory default Total Scale Factor is 00.3076 Take the Rate Scale Factor from Step three and divide by 60. For example if the Rate Scale factor from Step three is 017.720, the Total Scale Factor is 00.2953 Record the number here _____ and also below in “Step six” part h. For liters per minute Note: Factory default Total Scale Factor is 01.1645 Take the Rate Scale Factor from Step three and divide by 60.
Programming Batch Control The FMBC-2000 has a SPDT relay located inside the meter enclosure that controls the drum pump motor. When the required customer adjustable volume of liquid has passed through the meter, the relay deactivates and power to the drum pump motor is terminated. 1. To set batch amount value, press and hold down the 2. Press the button for at least two seconds. button seven times to scroll through screens to arrive at Batch Amount screen.
Figure 1 Figure 2 - Factory Default Chart Section 3 - Maintenance The FMBC-2000 Series was engineered for low maintenance; however, some conditions will cause increased wear on the paddle and/or possible damage to the unit. Damage caused by corrosives incompatible with the meters materials of construction or abrasive fluids is not covered under warranty. • Periodically remove the sensor from the molded in-line body and inspect for signs of wear and obstructions. Clean the paddle of any foreign material.
Section 4 - Warranty Finish Thompson, Inc (manufacturer) warrants this product to be free of defects in materials and workmanship for a period of one year from date of purchase by original purchaser. If a warranted defect, which is determined by manufacturer’s inspection, occurs within this period, it will be repaired or replaced at the manufacturer’s option, provided (1) the product is submitted with proof of purchase date and (2) transportation charges are prepaid to the manufacturer.