Miniature industrial relays 8 to16A
Technical data
Insulation according to EN61810-1
1 pole 2 pole
Nominal voltage of supply system VAC 230/400 230/400
Rated insulation voltage VAC 250 400 250 400
Pollution degree 3 2 3 2
Insulation between coil and contact set
Type of Insulation Reinforced (8mm) Reinforced (8mm)
Overvoltage category III III
Rated impulse voltage kV (1.2/50μs) 6 6
Dielectric strength VAC 4000 4000
Insulation between adjacent contacts
Type of insulation Basic
Overvoltage category III
Rated impulse voltage kV (1.2/50μs) 4
Dielectric strength VAC 2000
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection
Dielectric strength VAC/kV (1.2/50μs) 1000/1.5 1000/1.5
Conducted disturbance immunity
Burst (5…50)ns, 5kHz, on A1 - A2 according to EN61000-4-4 level 4 (4kV)
Surge (1.2/50μs) on A1 - A2 (differential mode) according to EN61000-4-5 level 3 (2kV)
Other data 46.61 46.52
Bounce time: NO/NC ms 2/6 1/4
Vibration resistance (10…150)Hz: NO/NC g 20/12 20/15
Shock resistance g 20 20
Power lost to the environment without contact current W 0.6 0.6
with rated current W 1.6 2
Recommended distance between relays mounted on PCB mm ≥5
Contact specification
F 46 - Electrical life (AC) v contact current
Type 46.52
F 46 - Electrical life (AC) v contact current
Type 46.61
Cycles
Resistive load - cosφ = 1
Inductive load - cosφ = 0.4
Cycles
Resistive load - cosφ = 1
Inductive load - cosφ = 0.4
H 46 - Maximum DC1 breaking capacity
46.61 limit current
46.52 limit current
DC breaking current (A)
DC voltage (V)
When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥100·10
3
can be expected.
In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.