Data Sheet

Functions
U = Supply voltage
S = Signal switch
= Output contact
LED
Type 86.00
LED
Type 86.30
Supply
voltage
NO output
contact
OFF Open
ON Open
ON
Open
(Timing in Progress)
ON Closed
Without
control signal = Start via contact in supply line (A1).
With
control signal = Start via contact into control terminal (B1).
Wiring diagram
Type 86.00
Without control signal
(AI) On-delay.
Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs when power is removed.
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
(SW) Symmetrical flasher (starting pulse on).
Apply power to timer. Output contacts transfer immediately
and cycle between ON and OFF for as long as power is
applied. The ratio is 1:1 (time on= time off).
With control signal
*
* With DC supply,
positive polarity has
to be conneted to B1
terminal (according to
EN60204-1).
Switch S should be
exclusively used to
provide the control
signal to terminal B1.
(Do not connect any
other load at this point).
(BE) Off-delay with control signal.
Power is permanently applied to the timer.
The output contacts transfer immediately on closure of the
Signal Switch (S). Opening the Signal Switch initiates the preset
delay, after which time the output contacts reset.
(CE) On- and off-delay with control signal.
Power is permanently applied to the timer.
Closing the Signal Switch (S) initiates the preset delay, after
which
time the output contacts transfer. Opening the Signal
switch initiates the same preset delay, after which time the
output contacts reset.
(DE) Interval with control signal on.
Power is permanently applied to the timer.
On momentary or maintained closure of Signal Switch (S),
the output contacts transfer, and remain so for the duration
of the preset delay, after which they reset.
(EE) Interval with control signal off.
Power is permanently applied to the timer.
On opening of the Signal Switch (S) the output contacts
transfer, and remain so for the duration of the preset delay,
after which they reset.
(FE) Interval with control signal on and off.
Power is permanently applied to the timer.
Both the opening and closing of the Signal Switch (S)
initiates the transfer of the output contacts. In both instances
the contacts reset after the delay period has elapsed.
Wiring diagram Type 86.30
(AI) On-delay.
Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs when power is removed.
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
6
II-2018www.findernet.com
H
86 SERIES
Timer modules
86
SERIES