Data Sheet

Ordering information
Example: 86 series multi-function timer module, (12…240)VAC/DC supply voltage.
8 6 . 0 0 . 0 . 2 4 0 . 0 0 0 0
Series
Type
0 = Multi-function (AI, DI, SW, BE, CE, DE, EE, FE)
3 = Bi-function (AI, DI)
No. of poles
See 40, 44, 46, 55, 56, 60 and 62series relays
Poles for chosen relay/socket combination -
according to chart below
Supply voltage
024 = (12…24)VAC/DC (86.30 only)
120 = (110…125)VAC (86.30 only)
240 = (12…240)VAC/DC (86.00 only)
240 = (12…48) V AC/DC
(86.00.0.240.0073 only)
240 = (230…240)VAC (86.30 only)
Supply version
0 = AC (50/60Hz)/DC
8 = AC (50/60Hz)
Combinations
Number of poles Relay type Socket type Timer module
1 40.31 95.P3/95.03 86.30
1 40.61 95.P5/95.05 86.30
1 46.61 97.P1/97.01 86.30
2 40.52/44.52/44.62 95.P5/95.05 86.30
2 46.52 97.P2/97.02 86.30
2 55.32 94.P4/94.02 86.30
2 56.32 96.02 86.30
2 60.12 90.02 86.00/86.30
2 62.32 92.03 86.00/86.30
3 55.33 94.P3/94.03 86.30
3 60.13 90.03 86.00/86.30
3 62.33 92.03 86.00/86.30
4 55.34 94.P4/94.04 86.30
4 56.34 96.04 86.00/86.30
Other data Timer ATEX versions
Code available Nominal tension Operating range Use temperature
86.00.0.240.0073 12-48 V AC/DC 10.2…60 V AC/DC –20…+50°C
86.30.0.024.0073 12-24 V AC/DC 9.6…33.6 V AC/DC –20…+50°C
Markings - ATEX versions - ATEX, II 3G Ex ec IIC Gc
MARKING
Specific marking of explosion protection
II
Component for surface plant (different from mines)
3
Category 3: normal level of protection
GAS
G
Explosive atmosphere due to presence of combustible gas vapour or mist
Ex ec
Increased security
IIC
Gas group
Gc
Equipment Protection Level
–20°C≤Ta≤+50°C
Ambient temperature
EPTI 17 ATEX 0264 U
EPTI: laboratory which issues the CE type certificate
17: year of issue of certificate
0264: number of CE type certificate
U: ATEX component
4
II-2018www.findernet.com
H
86 SERIES
Timer modules
86