Datasheet

2
86 Series - Timer modules
Example: 86 series multi-function timer module, (12...240)V AC/DC supply voltage.
Ordering information
Number of poles Relay type Socket type Timer module
1 40.31 95.03 86.30
1 40.61 95.05 86.30
1 46.61 97.01/97.51 86.30
2 40.52/44.52/44.62 95.05/95.55 86.30
2 46.52 97.02/97.52 86.30
2 55.32 94.02/94.54 86.30
2 56.32 96.02 86.30
2 60.12 90.02 86.00/86.30
2 62.32 92.03 86.00/86.30
3 55.33 94.03 86.30
3 60.13 90.03 86.00/86.30
3 62.33 92.03 86.00/86.30
4 55.34 94.04/94.54 86.30
4 56.34 96.04 86.00/86.30
Time scales
EMC specifications
Type of test Reference standard 86.00 86.30
Electrostatic discharge contact discharge EN 61000-4-2 4 kV n.a.
air discharge EN 61000-4-2 8 kV 8 kV
Radio-frequency electromagnetic field (80 ÷ 1,000 MHz) EN 61000-4-3 10 V/m 10 V/m
Fast transients (burst) (5-50 ns, 5 kHz) on Supply terminals EN 61000-4-4 4 kV 2 kV
Surges (1.2/50 µs) on Supply terminals common mode EN 61000-4-5 4 kV 2 kV
differential mode EN 61000-4-5 4 kV 1 kV
Radio-frequency common mode (0.15 ÷ 80 MHz) EN 61000-4-6 10 V 10 V
on Supply terminals
Radiated and conducted emission EN 55022 class B class B
Other data 86.00 86.30
Current absorption on signal control (B1) mA 1
Power lost to the environment without contact current W 0.1 (12 V) - 1 (230 V) 0.2
with rated current See 56, 60 and 62 series relays See 40, 44, 46, 55, 56, 60, 62
series relays
Technical data
Combinations
Supply voltage
024 = (12...24)V AC/DC (86.30 only)
120 = (110...125)V AC (86.30 only)
240 = (12...240)V AC/DC (86.00 only)
240 = (230...240)V AC (86.30 only)
Supply version
0 = AC (50/60 Hz)/DC
8 = AC (50/60 Hz)
Series
Type
0 = Multi-function (AI, DI, SW, BE, CE, DE, EE, FE)
3 = Bi-function (AI, DI)
No. of poles
See 40, 44, 46, 55, 56, 60 and 62 series relays
Poles for chosen relay/socket combination -
according to chart below
0 0 0 00 0 0
... .
24086
NOTE: Time scales and functions must be set before energising the timer.
To achieve the minimum time setting of 0.05 seconds it is necessary to use one of the functions with
control signal.
When setting very short times it may be necessary to take into account the operate time of the relay used.
II-2014, www.findernet.com
86
SERIES
Timers and Monitoring relays