Data Sheet

XI-2017, www.findernet.com
3
E
7P
SERIES
7P SERIES
Surge Protection Device (SPD)
SPD Type 1+2 Surge arrester range high
discharge capability with no following
current- single/three phase systems
Surge arresters, suitable for low-voltage
applications, to protect equipment against
overvoltage by direct lightning strike, induced
overvoltage and switching overvoltage
To be installed at the boundary of LPZ0- LPZ1
zones or higher
Versions with combination of varistor and high-
performance spark gap (GDT) ensures:
- high discarge current
- high insulation resistance that eliminates leakage
current
- no following current
Very low residual voltage
Replaceable modules
Upside down mounting possible (thanks to dual
terminal markings and new restraint system for
the replaceable module that permits its inversion)
Visual fault signalling: Healty/Replace
Double screw terminal
Remote status signalling contact:
Healty/Replace/Presence. Connector 07P.01 included
According to EN61643-11
35mm rail EN60715 mounting, 36mm each pole
7P.09.1.255.0100 SPD Type 1, GDT protection for
N-PE application only, for 3+1
configuration
7P.01.8.260.1025 SPD Type 1+2, varistor + GDT
unipolar protection suitable to
realize single phase or three phase
systems (230/400V) with the GDT
protection module (7P.09)
7P.02.8.260.1025 SPD Type 1+2 for single phase TT
and TN-S system. Varistor + GDT
protection L-N + GDT protection
N-PE
7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025
SPD Type 1
Spark gap module for N-PE
application in three phase
system, 3+1 configuration
Remote contact signalling of
GDT presence
Upside down mounting possible
Replaceable modules
SPD Type 1+2
Combination of varistor and
encapsulated spark gap (for
single or three phase systems)
Visual fault and remote
contact fault signalling
varistor/GDT status
Upside down mounting possible
Replaceable modules
SPD Type 1+2
Combination of varistor and
encapsulated spark gap (for
single phase systems)
Visual fault and remote contact
fault signalling varistor/GDT
status, N-PE GDT presence
Upside down mounting possible
Replaceable modules
7P.01.8.260.1025
For outline drawing see page 17
SPD specification N-PE L-N N-PE
Nominal voltage (U
N
) VAC 230 230
Maximum operating voltage (U
C
) VAC 255 260 260 255
Lightning impulse current (10/350μs) (I
imp
) kA 100 25 25 50
Nominal discharge current (8/20μs) (I
n
) kA 100 30 30 50
Maximum discharge current (8/20μs) (I
max
) kA 100 60 60 100
Voltage protection level (U
p
) kV 1.5 1.5 1.5 1.5
Ability to independently switch off
the following current (I
fi
) A 100
No following
current
No following
current 100
I
PE
uA
<4 <4 <4
TOV 120 min L-N VAC
440 440
TOV5 s L-N VAC
335 335
TOV200 ms N-PE VAC
1200 1200
Response time (t
a
) ns 100 100 100 100
Short-circuit proof at maximum
overcurrent protection - I
SSCR
kA
rms
50 50
Maximum overcurrent protection (fuse rating gL/gG) 250A 250A
Maximum overcurrent protection for serial connection 125 A gL/gG 125 A gL/gG
Replacement module code 7P.00.1.000.0100 7P.00.8.260.0025 7P.00.8.260.0025 7P.00.1.000.0050
Other technical data
Ambient temperature range °C –40…+80
Protection degree IP20
Wire size solid cable stranded cable
mm
2
1x2.5…1x50 1x2.5…1x35
AWG 1x13…1x1 1x13…1x2
Wire strip length mm 11
Screw torque Nm 4
Remote status signalling contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT) 1 CO (SPDT)
Rated current AAC/DC 0.5/0.1 0.5/0.1 0.5/0.1
Rated voltage VAC/DC 250/30 250/30 250/30
Wire size (07P.01) solid cable stranded cable solid cable stranded cable solid cable stranded cable
mm
2
1.5 1.5 1.5 1.5 1.5 1.5
AWG 16 16 16 16 16 16
Approvals (according to type)