Data Sheet
XI-2017, www.findernet.com
13
E
7P
SERIES
7P SERIES
Surge Protection Device (SPD)
SPD Type 2+3 with combination of coarse and
fine suppression for 2 wires telecomunication
and signalling network
• Suitable for the protection of 2 wires data lines
and telecommunication interface allowing
continuity of the shield
• Permits serial connection optimizing the fine
protection of longitudinal overvoltage
(core-PG) and lateral overvoltage (core-core)
• Conform to EN61643-21+A1,A2:2013,
ENIEC61643-21+A1,A2:2012 C2,C3
• DIN rail mounting
7P.62.9.009.0485
• Suitable for the protection of RS485 data
lines of inverter, PLC, energy meters or other
interfaces
7P.62.9.036.0005
• Suitable for the protection of fire detection
systems, telecommunications interfaces and
2-wire data lines
7P.62.9.009.0485 7P.62.9.036.0005
• SPD Type 2+3
• Protection of RS485 data lines,
telecommunication and other Bus lines
• SPD Type 2+3
• Protection of fire detection systems,
telecommunication and other data/Bus lines
SH
SH
SH
SH
For outline drawing see page 20
SPD specification
Nominal voltage (U
N
) VDC 6 24
Maximum operating voltage (U
C
) VDC 8.5 36
Nominal load current (I
L
) A 0.5 0.5
C2 nominal discharge current
(8/20μs) core-core (I
n
) kA 5 5
C2 total discharge current
(8/20μs) cores-PE (C) kA 10 10
C2 voltage protection level mode
core-core @ I
n
(U
p
) V 18 50
C2 voltage protection level mode
core-PE @ I
n
(U
p
) V 30 65
C3 voltage protection level mode
core-core @1kV/μs (U
p
) V 12 45
C3 voltage protection level mode
core-PE @1kV/μs (U
p
) V 15 45
Response time core-core/core-PE (ta) ns 1/1 1
Serial resistance per core (R) Ω 1.6 1.6
Treshold frequency core-core (f) MHz 1 4
Other technical data
Range of operating temperature °C −40…+70 −40…+70
Degree of protection IP 20 IP 20
Wire size solid cable stranded cable solid cable stranded cable
mm
2
4 2.5 4 2.5
AWG 12 14 12 14
Approvals (according to type)