Data Sheet

E
Accessories for 72.01 and 72.11
072.11
Floor water sensor, designed for the detection and reporting of the presence of floor surface water. 072.11
Technical data
Electrode material stainless steel (AISI 301)
Wire capability of terminals
Max screw torque  Nm 0.8
Max. wire size solid cable stranded cable
mm
2
1x6 / 2x6 1x6 / 2x4
AWG 1x10 / 2x10 1x10 / 2x12
Wire strip length  mm 9
Other data
Distance between electrodes and floor  mm 1
Floor fixing screw diameter Maximum M5
Maximum cable diameter  mm 10
Maximum length of cable connecting sensor to relay  m 200 (with capacitance of 100nF/km)
Max. liquid temperature  °C +100
Floor surface water sensor for connection to electrode terminals 
(B1 and B3) of 72.01 or 72.11 level control relay, set in Emptying 
function (ES or E respectively).
For ice bank control in refrigeration systems it is suggested to 
use the high sensitivity (5…450)kΩ types - 72.01.8.024.0002 or 
72.01.8.230.0002.
Function
Z1, Z2 only for types 72.11
072.51
Electrode holder with two pole connector, one connected directly to the electrode and the 
second connected to the grounded installation thread. Suitable for metal tank with G3/8” linkage.
Electrode not incuded. Order appropriate number of electrodes holders - additional to the relay. 072.51
Technical data
Max liquid temperature  °C +100
Max tank pressure  bar 12
Cable grip  mm Ø≤6
Electrode material stainless steel (AISI304)
12
IV-2018,www.findernet.com
72 SERIES 
Monitoring relays
72
SERIES 