Data Sheet
A
Power relays 1 and 2 pole for direct PCB or 
socket mount
Type 40.31/51
 - 1 CO 12 A (3.5mm pin pitch)
 - 1 CO 12 A (5.0mm pin pitch)
Type 40.52
 - 2 CO 8A  (5.0mm pin pitch)
Type 40.61
 - 1 CO 16 A (5.0mm pin pitch)
• Pin length 3.5 mm for PCB mount
• Pin length 5.3 mm for Plug-in mount
• DC coils (650 mW or 500 mW)
• Cadmium-free contact material available
• 8 mm Creepage and Clearance, 6 kV (1.2/50µs)
between coil and contact
• Meets EN 60335-1 glow wire requirements
• 95 series sockets for PCB or 35 mm rail 
mounting (EN 60715) with Screw, Screwless or 
Push-in terminals
• Coil Indication and EMC suppression modules 
99 series and Timer module 86.30 options
• Environmental protection: 
RT II - flux proof (Standard) 
RT III - wash tight (Option)
40.31/51 40.52 40.61
• 1 CO 12 A on PCB, 10 A with 
socket
• 3.5mm pin pitch (40.31), 
5.0mm pin pitch (40.51)
• PCB or 95 Series socket mount 
• 2 CO 8 A
• 5.0mm pin pitch
• PCB or 95 Series socket mount
• 1 CO 16 A
• 5.0mm pin pitch
• PCB or 95 Series socket mount 
40.31
40.51
Copper side view
Pin length 3.5mm for PCB only
Pin length 5.3mm for PCB or 
sockets
See ordering information
Copper side view
Pin length 5.3mm for PCB or 
sockets
See ordering information
Copper side view
Pin length 3.5mm for PCB only
Pin length 5.3mm for PCB or 
sockets
See ordering information
* Mounted on sockets ≤10A
**   With  the  AgSnO
2 
material the 
maximum peak
current is 120A- 5ms on normally open 
contact.
For UL ratings see: 
“General technical information” page V
For outline drawing see page 12
Contact specification
Contact configuration 1 CO (SPDT) 2 CO (DPDT) 1 CO (SPDT)
Rated current/Maximum peak current  A 12*/20 8/15 16/30**
Rated voltage/ 
Maximum switching voltage  VAC
250/400 250/400 250/400
Rated load AC1  VA 3000 2000 4000
Rated load AC15 (230VAC)  VA 1000 750 1000
Single phase motor rating (230VAC)  kW 0.55 0.37 0.55
Breaking capacity DC1: 30/110/220V  A 12/0.6/0.25 8/0.6/0.25 16/0.6/0.25
Minimum switching load  mW (V/mA) 300 (5/5) 300 (5/5) 500 (10/5)
Standard contact material AgNi AgNi AgCdO
Coil specification
Nominal voltage (U
N
) VAC (50/60Hz) — — —
VDC 5 - 6 - 7 - 9 - 12 - 14 - 18 - 21 - 24 - 28 - 36 - 48 - 60 - 90 - 110 - 125
Rated power DC/sensitive DC  W 0.65/0.5 0.65/0.5 0.65/0.5
Operating range AC — — —
DC/sensitive DC (0.73…1.5)U
N
/(0.73…1.5)U
N
(0.73…1.5)U
N
/(0.73…1.5)U
N
(0.73…1.5)U
N
/(0.8…1.5)U
N
Holding voltage  DC 0.4
U
N
0.4
U
N
0.4
U
N
Must drop-out voltage  DC 0.1
U
N
0.1
U
N
0.1
U
N
Technical data
Mechanical life  cycles 10·10
6
10·10
6
10·10
6
Electrical life at rated load AC1  cycles 200·10
3
100·10
3
100·10
3
Operate/release time  ms 7/3 (10/3 sensitive) 7/3 (12/4 sensitive) 7/3 (10/3 sensitive)
Insulation between coil 
and contacts (1.2/50µs)  kV
6 (8mm) 6 (8mm) 6 (8mm)
Dielectric strength 
between open contacts  VAC
1000 1000 1000
Ambient temperature range  °C –40…+85 –40…+85 –40…+85
Environmental protection RT II*** RT II*** RT II***
Approvals (according to type)
*** See general technical information “Guidelines for automatic flow solder processes” page II.
3
VI-2018, www.findernet.com
40
SERIES 
40 SERIES 
PCB/Plug-in relays 8 - 10 - 12 - 16A