Datasheet
5
60 Series - General purpose relays 6 - 10 A
Technical data
Contact specification
F 60 - Electrical life (AC) v contact current
Cycles
H 60 - Maximum DC1 breaking capacity
DC voltage (V)
DC breaking current (A)
contacts in series
Resistive load - cosϕ = 1
Inductive load - cosϕ = 0.4
• When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥ 100·10
3
can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Nominal Coil Operating range Resistance Rated coil
voltage code
consumption
U
N
U
min
U
max
R
I at U
N
(50Hz)
VVVΩ mA
6 8.006 4.8 6.6 4.6 367
12 8.012 9.6 13.2 19 183
24 8.024 19.2 26.4 74 90
48 8.048 38.4 52.8 290 47
60 8.060 48 66 450 37
110 8.110 88 121 1,600 20
120 8.120 96 132 1,940 18.6
230 8.230 184 253 7,250 10.5
240 8.240 192 264 8,500 9.2
400 8.400 320 440 19,800 6
Nominal Coil Operating range Resistance Rated coil
voltage code
consumption
U
N
U
min
U
max
R I at U
N
VVVΩ mA
6 9.006 4.8 6.6 28 214
12 9.012 9.6 13.2 110 109
24 9.024 19.2 26.4 445 53.9
48 9.048 38.4 52.8 1,770 27.1
60 9.060 48 66 2,760 21.7
110 9.110 88 121 9,420 11.7
125 9.125 100 138 12,000 10.4
220 9.220 176 242 37,300 5.8
AC coil data
DC coil data
Coil specifications
Insulation according to EN 61810-1 2 pole 3 pole
Nominal voltage of supply system V AC 230/400 230/400
Rated insulation voltage V AC 250 400 250 400
Pollution degree 3 2 3 2
Insulation between coil and contact set
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 4 3.6
Dielectric strength V AC 2,000 2,000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 4 3.6
Dielectric strength V AC 2,000 2,000
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 µs) 1,000/1.5 1,000/1.5
Conducted disturbance immunity
Burst (5...50)ns, 5 kHz, on A1 - A2 EN 61000-4-4 level 4 (4 kV)
Surge (1.2/50 µs) on A1 - A2 (differential mode) EN 61000-4-5 level 4 (4 kV)
Other data
Bounce time: NO/NC ms 1/4
Vibration resistance (5…55)Hz: NO/NC g 22/22
Shock resistance g 20
Power lost to the environment without contact current W 1.3 1.3
with rated current W 2.7 (60.12, 60.62) 3.4 (60.13, 60.63)
VII-2012, www.findernet.com