Data Sheet

K
Ordering information
Example: 26 series screw terminal, panel mount relay, double phase switch 2 NO (DPST-NO) 10A contacts, coil rated 12VAC.
2 6 . 0 2 . 8 . 0 1 2 . 0 . 0 . 0 . 0
Series
Type
0 = Screw terminal
No. of poles
1 = Single phase switch 1 NO (SPST-NO)
2 = Double phase switch 2 NO (DPST-NO)
3 = Double phase switch 1 NO + 1 NC (SPST-NO + SPST-NC)
4 = 4 sequences double phase switch 2 NO (DPST-NO)
6 = 3 sequences double phase switch 2 NO (DPST-NO)
8 = 4 sequences double phase switch 2 NO (DPST-NO)
Coil voltage
See coil specifications
Coil version
8 = AC (50Hz)
Technical data
Insulation
Dielectric strength
between supply and contacts
VAC
3500
between open contacts
VAC
2000
between adjacent contacts
VAC
2000
Other data 26.01, 26.03, 26.08 26.02, 26.04, 26.06
Power lost to the environment
with rated current and coil de-energised W 0.9 1.8
Screw torque Nm
0.8 0.8
Max. wire size solid cable stranded cable solid cable stranded cable
mm
2
1x4 / 2x2.5 1x2.5 / 2x2.5 1x4 / 2x2.5 1x2.5 / 2x2.5
AWG 1 x 12 / 2 x 14 1x14 / 2x14 1x12 / 2x14 1x14 / 2x14
Coil specifications
AC version data
Nominal
voltage
U
N
Coil
code
Operating range Resistance
Consumption
I at U
N
(50Hz)
U
min
U
max
R
V V V
Ω
mA
12 8.012 9.6 13.2 17 370
24 8.024 19.2 26.4 70 180
48 8.048 38.4 52.8 290 90
110 8.110 88 121 1500 40
230 8.230 184 253 6250 20
Type
Number
of steps
Sequence
1 2 3 4
26.01 2
26.02 2
26.03 2
26.04 4
26.06 3
26.08 4
4
X-2017, www.findernet.com
26 SERIES
Step relays 10A
26