Solar inverter solutions for building applications

41 Page header
Technical data and types
Type code PVS-100-TL
Wiring Box version SX, SX2 SY, SY2 Standard S2
Physical
Environmental protection rating IP 66 (IP54 for cooling section)
Cooling Forced air
Dimension (H x W x D) 869x1086x419 mm / 34.2” x 42.7” x 16.5”
Weight
70kg / 154 lbs for power module ; ~55kg / 121 lbs for wiring box
Overall max 125 kg / 276 lbs
Mounting system Mounting bracket vertical & horizontal support
Safety
Isolation level Transformer-less
Marking CE
Safety and EMC standard IEC/EN 62109-1, IEC/EN 62109-2, EN 61000-6-2, EN 61000-6-4
Grid standard (check your sales channel for availability)
CEI 0-16, CEI 0-21, IEC 61727, IEC 62116, IEC 60068, IEC 61683, JORDAN IRR-DCC-MV, DRRG/
DEWA, Chile LV/MV, Belg C10-C11, EN50438 Generic +Ireland, EN50549-1/2, CLC-TS50549-1/2, AS/
NZS4777.2, UK G59/3, EREC G99-1, MEA, PEA, ISO-IEC Guide 67 (system 5), NRS 097-2-1, P.O. 12.3,
ITC-BT-40, UNE 206006 IN, VDE-AR-N 4105, VDE-AR-N 4110, VDE-AR-N 4120, VDE V 0-126-1-1,
VFR 2019, UTE C15-712-1, Taiwan
Available products variants
Inverter power module PVS-100-TL-POWER MODULE
Input with 24 quick fit connectors pairs + String fuses (both
positive and negative pole) + DC disconnect switches + AC
disconnect switch + AC and DC overvoltage surge arresters
(Type II) + individual string monitoring (24 ch.)
WB -SX2-PVS-100-TL
Input with 24 quick fit connectors pairs + String fuses (positive
pole) + DC disconnect switches + AC and DC overvoltage surge
arresters (Type II) + MPPT level input current monitoring (6 ch.)
WB -SX-PVS-100-TL
Input with 24 quick fit connectors pairs + String fuses (both
positive and negative pole) + DC disconnect switches + AC
disconnect switch + AC and DC overvoltage surge arresters
(Type II for AC and Type I+II for DC) + individual string monitoring
(24 ch.)
WB -SY2-PVS-100-TL
Input with 24 quick fit connectors pairs + String fuses (positive
pole) + DC disconnect switches + AC and DC overvoltage surge
arresters (Type II for AC and Type I+II for DC) + MPPT level input
current monitoring (6 ch.)
WB -SY-PVS-100-TL
Input with cable gland + DC disconnect switch + AC
disconnect switch + AC and DC overvoltage surge arresters
(Type II) + MPPT level input current monitoring
WB-S2-PVS-100-TL
Input with cable gland + AC and DC overvoltage surge arresters
(Type II) + MPPT level input current monitoring
WB-PVS-100-TL
Optional available
AC Plate, Single Core Cables Plate with 5 individual AC cable glands: 4 x M40: Ø 19...28mm, 1 x M25: Ø 10...17mm
AC Plate, Multi Core Cables Plate with 2 individual AC cable glands: 1 x M63: Ø 37…53mm, 1 x M25: Ø 10...17mm
PVS-100/120 Pre-Charge Board Kit Night time operation with restart capability
PVS-100/120 Grounding Kit
6)
Allow to connect the negative input pole to ground
1) Maximum number of opening 5 under overloading
2) Please refer to the document “String inverters – Product manual appendix”
available at www.fimer.com for information on the quick-fit connector brand
and model used in the inverter
3) Maximum fuse size supported 20A. Additionally two strings input per MPPT
supports 30A fuse size for connecting two strings per input
4) The AC voltage range may vary depending on country specific country grid
standard
5) The Frequency range may vary depending on specific country grid standards
6) When grounding-kit is installed, Residual Current Monitoring does not fully
operate. Inverter must be installed and operate in “restricted areas (access
limited to qualified personnel)” according to IEC 62109-2
Remark. Features not specifically listed in the present data sheet are not
included in the product