Solar inverter solutions for building applications
32 Page header
Type code PVS-20-TL (2MPPT) PVS-20-TL (4MPPT) PVS-30-TL PVS-33-TL
Input side
Absolute maximum DC input voltage
(Vmax,abs)
1100V
Start-up DC input voltage (Vstart) 250…500V (default 430V)
Operating DC input voltage range
(Vdcmin...Vdcmax)
200-1000 V
Rated DC input voltage (Vdcr) 620V
Rated DC input power (Pdcr) 20500 W 20500 W 30600 W 33700 W
Maximum photovoltaic power recom-
mended (PPV, max)
30000 Wp 34000 Wp 44000 Wp 48000 Wp
Number of independent MPPT 2 4 4 4
Maximum DC input current (Idcmax) for
each MPPT
2x26A 2x26A + 2x22A 2x26A + 2x22A 2x26A + 2x22A
Maximum DC input power for each MPPT
(PMPPT,max)
2x12000W 2x12000W + 2x10000W 2x12000W + 2x10000W 2x12000W + 2x10000W
MPPT input DC voltage range (VMPPTmin ...
VMPPTmax) at Pacr
460-850V
Maximum input short circuit current for
each MPPT
40A
1)
Number of DC inputs pairs for each
MPPT
2
DC connection type PV quick fit connector
Input protection
Reverse polarity protection Yes
Input over voltage protection for each
MPPT
SPD Type II / Type I+II (optional)
Isolation control Yes, according local regulation
Output side
AC grid connection type Three-phase (3W+PE or 4W+PE)
Earthing system TN-S, TN-C, TN-CS, TT TN-S, TN-C, TN-CS, TT TN-S, TN-C, TN-CS, TT TN-S, TN-C, TN-CS, TT and IT
2)
Rated AC power (Pacr @cosφ=1 )
20000 W 20000 W 30000 W 33000 W
Maximum AC output power (Pacmax @
cosφ=1)
22000 W up to 30°C
3)
22000 W up to 30°C
3
) 33000 W up to 30°C
3)
36300 W up to 30°C
3)
Maximum apparent power (Smax) 22000 VA up to 30°C
4)
22000 VA up to 30°C
4)
33000 VA up to 30°C
4)
36300 VA up to 30°C
4)
Maximum reactive power (Qmax) 20000 VAR 20000 VAR 30000 VAR 33000 VAR
Nominal power factor and adjustable
range
> 0.995; 0…1 inductive/capacitive
Rated AC grid voltage (Vac,r) 380V, 400V
5)
Maximum AC output current (Iac,max) 33,4 A 33,4 A 50,1 A 55,1 A
Rated output frequency (fr) 50 Hz / 60 Hz
Output frequency range (fmin...fmax) 47...53 Hz / 57…63 Hz (6)
Total current harmonic distortion <3%
Maximum AC cable 35 mm2 cupper/aluminum
AC connection type Detachable Terminal Block
Output protection
Anti-islanding protection According to local standard
Maximum external AC overcurrent
protection
63 A 63 A 80 A 80 A
Output overvoltage protection SPD Type II
Operating performance
Maximum efficiency (ηmax)
98,4% 98,4% 98,4% 98,4%
Euro efficiency (ηEURO)
98,2% 98,2% 98,2% 98,2%
Communication
Embedded communication interfaces Dual Ethernet port, WLAN, advanced RS-485 port (optional)
Communication protocol Modbus TCP Sunspec, Modbus RTU Sunspec (optional)
User Interface LEDs, Web User Interface, Installer APP, Display (optional)
Cloud services Aurora Vision® Plant Management Platform, Rest API
Advanced functions Embedded export limitation control (in combination with external meter), 24h self consuption monitoring