Solar inverter solutions for building applications
21 Page header
1) Refer to the document “String inverter – Product Manual appendix” avail-
able at www.fimer.com/solarinverters to know the brand and the model of the
quick fit connector”
2) For VDE-AR-N 4105 setting, maximum active power of 4600 W and maximum
apparent power of 4600 VA
3) The AC voltage range may vary depending on specific country grid standard
4) The Frequency range may vary depending on specific country grid standard
5) As per IEEE 802.11 b/g/n standard
6) Refer to the document “Meters supported by FIMER string inverters and
the VSN700-05 Data Logger”, available at
www.fimer.com, to know the complete compatible meter list
Remark. Features not specifically listed in the present data sheet are not
included in the product
Technical data and types
Battery unit REACT2-BATT
Modules manufacturer Samsung
Battery type Li-Ion
Total energy 4 kWh
Operating DC voltage range 170-575 V
Absolute maximum DC voltage 575 V
Module voltage 200 V
Deep of discharge (DoD) 95%
Charge power 1.6 kW
Discharge power 2 kW
Environmental
Enviromental protection rating IP 54 (suggested indoor installation for preserving battery life time)
Ambient temperature range -20...+55°C (power derating occurs out of suggested ambient temperature range)
Suggested ambient temperature +0 to +40 °C
Relative humidity 4…100 % condensing
Physical
Cooling Natural
Dimension (H x W x D) 740 mm x 490 mm x 229 mm
Weight < 50 kg
Mounting system Wall bracket
Safety
Marking CE
Safety IEC 62619, UN38.3, UN3480
Compatible meters
REACT-MTR-1PH Single-phase, 20 A
ABB B21
6)
Single-phase, 65 A
ABB B23
6)
Three-phase, 65 A
ABB B24
6)
Three-phase, External CT (opt.)
ABB A43
6)
Three-phase, 80 A
ABB A44
6)
Three-phase, External CT (opt.)
Technical data and types
Physical
Environmental protection rating IP65
Cooling Natural
Dimension (H x W x D) 740 mm x 490 mm x 229 mm
Weight < 22 kg
Mounting system Wall bracket
Safety
Isolation level Transformerless
Marking CE (50 Hz only)
Safety and EMC standard
IEC/EN 62109-1, IEC/EN 62109-2, IEC 62477-1, EN 61000-6-2, EN 61000-6-3, EN 61000-3-2, EN 61000-
3-3, EN61000-3-11, EN61000-3-12
Grid standard (check your sales channel for availability)
CEI 0-21, DIN V VDE V 0126-1-1, VDE-AR-N 4105, G83/2, G59/3, G98/1, G99/1, EN 50549-1,
RD 413, AS/NZS 4777.2, C10/11, IEC 61727, IEC 62116
Other features
Load manager Yes, with two integrated relays
AC backup output, off grid Yes
Battery charge from AC Yes, it can be enabled
AC-coupled feature Yes, settable during commissioning
REACT2-UNO-3.6-TL
REACT2-UNO-5.0-TL
Inverter