Installation guide
24
A
ppendix
Glossary
HVAC ………................ Heating, ventilating, and air conditioning
Dirty Air Filter ............... An air filter which has been in use and has collected some amount of dirt
or dust particles that discolor the filter fibers or element but do not
substantially affect the air flow through it.
Clogged Air Filter ......... An air filter which has collected a sufficient amount of dirt or dust particles
to not only discolor the filter fibers or element but decrease the air flow
through the filter as well. The
FILTERSCAN
WiFi Air Filter Monitor
typically identifies a filter as clogged when the differential pressure within
an HVAC system increases to 1.5 to 2 times the initial differential pressure
identified when the unit was calibrated with a clean filter.
Monitor ......................... The sensor voltage detection and signal processing portion of the system.
AirFilterSentry............... The application software and database residing on the Cloud Server that
provides all operational aspects of the
AirFilterSentry
Notification
Service.
Cloud Server ................. The computer server on which the
AirFilterSentry
Notification Service
resides and operates. The hosting service ensures database backups and
redundancy to provide maximum up-time of their systems.
MAC Address ............... Media Access Control unique identifier assigned to the WiFi radio within
the
FILTERSCAN
WiFi Air Filter Monitor
.
Indicators
Green STATUS LED...... The blinking Green STATUS LED at the
FILTERSCAN
WiFi Air Filter
Monitor
indicates normal operation.
Yellow STATUS LED..... The blinking Yellow STATUS LED at the
FILTERSCAN
WiFi Air Filter
Monitor
indicates a process is occurring and can also indicate a low
battery condition at the Monitor or Receiver.
Red STATUS LED ........ The Red STATUS LED at the
FILTERSCAN
WiFi Air Filter Monitor
is an alarm indicator which blinks whenever an alarm condition occurs.
Beeper .......................... The audible beeper at the
FILTERSCAN
WiFi Air Filter Monitor
is an
alarm indicator which beeps whenever certain alarm conditions occur.
Local Alarm Indications
Monitor/Transmitter Alarm Indications
Alarm Condition Alarm Indication Clear Alarm Procedure
Normal Operation
STATUS LED flashes green every minute.
None
Clogged Filter
STATUS LED flashes red five times every
ten minutes. Beeper sounds with LED flash.
Replace Filter and
Recalibrate
Low Battery
STATUS LED flashes yellow every minute.
Replace Batteries
Sensor Failure
STATUS LED continuously on red.
Contact CleanAlert at 888-
414-3569