Datasheet

TEMPERATURE
AND
HUMIDITY
COMPENSATION
METHOD
As was previously mentioned,
Sensor
resistance (Rs) is dependent upon the
ambient temperature and humidity. Accordingly, this phenomenon will result
in a
fluctuation
of the alarming
Point.
Possible variations in the
effects
of temperature and humidity changes are illustrated in
TableV.
This Variation in
Sensor
Performance, however, is primarily related to the
measure of Absolute Humidity in the detecting area.
It is therefore
rec-
ommended that you determine the mean or
average
temperature and humidity
values in your projected
detector
sales
or distribution area, to be able to
compensate for seasonal variations in the alarming
Point.
The most
effi-
cient
and economical way we have found to
achieve
this
compensation
is to
carefully control the temperature dependency of the circuit.
This
Point
is
discussed below.
Table V illustrates possible variations in alarming
Points
in both
compen-
sated and non-compensated circuits.
Another way of interpreting these
varia-
tions is to say that if
R/Ro
= 1 at 20°C (65% R.H.) then at -10°C (65%
R.H.)
R/Ro
is 1.6 and at 35°C
(65% R.H.) is
0.9.
The
actual
VRI
can.be
expressed as:
2.5 V at
ZOOC,
1.9V
at-10°C
and 2.6 V at
35OC.
To compensate for these variations in temperature and humidity we suggest
using
a negative characteristic thermistor (Rt).
In this example circuit,
the Vr is automatically adjusted as a result of temperature changes. As
was mentioned, Rt is set at
2.5V
for
20°C
in this circuit.
At -10°C Vr
will
self-adjust
to
2,1V,
while at 35°C
it will go to
2.7V.
The
differente
between
Vm
and Vr is
detected by the following Comparator
12.
Therefore you
tan
get rid of the seasonal Variation of alarming
Points
hich
are
caused
by temperature and humidity fluctuations by adjusting Vr.
With the
application
of a temperature
compensation
circuit
you will
be
able
to control the alarming
Points
as illustrated in
Table
V,
The temperature coefficient of the thermistor is larger than that of the
Sensor,
therefore we have to
adjust
the coefficient of the thermistor by
adjusting
RZ
and
RS.
A
final
important consideration is the
actual
place
where the thermistor is
placed
in the circuit.
You should not
install
it near heat dissipating
components such as the transformer or the Sensor.
Also it should not be
installed in a
Position
where it is
likely to receive a strong wind, as
this will also
effect
the temperature characteristics of the Sensor.
(17)