Technologies Ethernet Port Start-Up Guide
FieldServer FS-X25 Start-Up Guide               Page 3 of 12 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com 
1  EQUIPMENT SET-UP 
1.1  Supplied equipment 
FS-X25 Series FieldServer. 
  loaded with Modbus  RTU driver,  SMT  Ethernet driver  and any  other  drivers ordered. A default 
configuration  file has already been loaded onto the  FieldServer.   Check  the Driver Manual and  the 
FieldServer Configuration Manual for further information on this file. 
USB Flash Drive loaded with:  
  FS-X25 Series Start-up Guide 
  FieldServer Configuration Manual 
  FieldServer Utilities Manual 
  All FieldServer Driver Manuals 
  Support Utilities 
  Any additional folders related to special files configured for a specific FieldServer 
  Additional components as required - See Driver Manual Supplement for details 
Accessories: 
  7-ft Cat5 cable with RJ45 connectors at both ends (Part # FS-8915-10) 
  Power Supply 
1.2  Mounting 
The FS-X25 Series FieldServer is supplied with an accessory bag which allows selection of adhesive feet (for 
standing on a shelf) or mounting plates for wall or panel mount.  A DIN Rail Mounting Kit (P/N FS-8915-28) may be 
ordered separately. 
1.3  Wiring 
5-30VDC must be connected to the terminal block 
1.3.1  Compliance with UL Regulations  
For UL compliance, the following instructions must be met when operating the FieldServer. 
  The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature 
range. 
  The interconnecting power connector and power cable shall: 
  Comply with local electrical code. 
  Be suited to the expected operating temperature range. 
  Meet the current and voltage rating for the FieldServer/Net  
  Furthermore, the interconnecting power cable shall: 
  Be of length not exceeding 3.05m (118.3”) 
  Be constructed of materials rated VW-1 or FT-1 or better. 
  If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed 
in a Restricted Access Area requiring a key or a special tool to gain access 
  This device must not be connected to a LAN segment with outdoor wiring. 